FIR11-00247
| INSP-Sprinkler Rough-in | 9/9/2011 | 9/9/2011 | 9/9/2011 5:58:32 PM | P | PART |
|
|
UG fire supply line flush completed satisfactory.
|
BLD11-00390
| FIRE-Final Inspection | 9/9/2011 | 9/9/2011 | 9/9/2011 5:31:51 PM | A | PASS |
|
|
|
FIR11-00330
| INSP-Final Inspection | 9/9/2011 | 9/9/2011 | 9/9/2011 5:31:20 PM | P | CANC |
|
|
Overbooked
|
FIR11-00242
| INSP-Sprinkler Rough-in | 9/9/2011 | 9/9/2011 | 9/9/2011 4:37:21 PM | P | CANC |
|
|
Overbooked
|
FIR11-00480
| INSP-Sprinkler Rough-in | 9/9/2011 | 9/9/2011 | 9/9/2011 4:24:00 PM | P | NH |
|
|
No access to the remodel space at the time of inspection. Discussed scope of work with the contractor.
|
BLD11-00689
| FIRE-Final Inspection | 9/9/2011 | 9/9/2011 | 9/9/2011 4:22:22 PM | P | FAIL |
|
|
Remove the manual thumbturn at the main entry/exit door. Remainder of life safety okayed.
|
BLD11-01935
| FIRE-Final Inspection | 9/9/2011 | 9/9/2011 | 9/9/2011 4:20:49 PM | P | FAIL |
|
|
See items #1,2,3,and 4 on list of general requirements attatched to the permit documents for items needed prior to final approval.
|
FIR11-00362
| INSP-Final Inspection | 9/8/2011 | 9/9/2011 | 9/9/2011 4:17:53 PM | A | NR |
|
|
Not ready for final inspection per conversation with contractor. Discussed requirements for acceptance testing per IFC.
|
BLD10-02330
| FIRE-Final Inspection | 9/8/2011 | 9/9/2011 | 9/9/2011 4:15:43 PM | A | FAIL |
|
|
Missing premise identification, need to post fire extinguishers, site construction underway, project not in condition for final life safety at this time.
|
FIR11-00391
| INSP-Final Inspection | 9/8/2011 | 9/9/2011 | 9/9/2011 4:12:18 PM | A | PART |
|
|
Fire sprinkler permit okay for final pending verification the existing system is current with and annual inspection per NFPA 25.
|
FIR11-00430
| INSP-Final Inspection | 9/8/2011 | 9/9/2011 | 9/9/2011 4:11:08 PM | A | FAIL |
|
|
HVAC unit not functional to enable testing of the new duct smoke detector, also need to post updated points map at the RA, no access to the FACP room.
|
BLD11-01683
| FIRE-Final Inspection | 9/8/2011 | 9/9/2011 | 9/9/2011 4:06:58 PM | A | NR |
|
|
Fire life safety final pending project related fire alarm permit final. Noted common restrooms are not finished. Remainder of life safety items including exit signs/EM lights, fire extinguishers, building address, and door hardware appear acceptable.
|
FIR08-00239
| INSP-Sprinkler Rough-in | 9/8/2011 | 9/9/2011 | 9/9/2011 4:03:14 PM | A | PART |
|
|
Pendent heads at the 2nd, 3rd and 4th floor corridors of building three approved for cover.
|