Inspections for the day of: Friday, September 9, 2011.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR11-00247 INSP-Sprinkler Rough-in9/9/20119/9/20119/9/2011 5:58:32 PMPPART
UG fire supply line flush completed satisfactory.
BLD11-00390 FIRE-Final Inspection9/9/20119/9/20119/9/2011 5:31:51 PMAPASS
FIR11-00330 INSP-Final Inspection9/9/20119/9/20119/9/2011 5:31:20 PMPCANC
Overbooked
FIR11-00242 INSP-Sprinkler Rough-in9/9/20119/9/20119/9/2011 4:37:21 PMPCANC
Overbooked
FIR11-00480 INSP-Sprinkler Rough-in9/9/20119/9/20119/9/2011 4:24:00 PMPNH
No access to the remodel space at the time of inspection. Discussed scope of work with the contractor.
BLD11-00689 FIRE-Final Inspection9/9/20119/9/20119/9/2011 4:22:22 PMPFAIL
Remove the manual thumbturn at the main entry/exit door. Remainder of life safety okayed.
BLD11-01935 FIRE-Final Inspection9/9/20119/9/20119/9/2011 4:20:49 PMPFAIL
See items #1,2,3,and 4 on list of general requirements attatched to the permit documents for items needed prior to final approval.
FIR11-00362 INSP-Final Inspection9/8/20119/9/20119/9/2011 4:17:53 PMANR
Not ready for final inspection per conversation with contractor. Discussed requirements for acceptance testing per IFC.
BLD10-02330 FIRE-Final Inspection9/8/20119/9/20119/9/2011 4:15:43 PMAFAIL
Missing premise identification, need to post fire extinguishers, site construction underway, project not in condition for final life safety at this time.
FIR11-00391 INSP-Final Inspection9/8/20119/9/20119/9/2011 4:12:18 PMAPART
Fire sprinkler permit okay for final pending verification the existing system is current with and annual inspection per NFPA 25.
FIR11-00430 INSP-Final Inspection9/8/20119/9/20119/9/2011 4:11:08 PMAFAIL
HVAC unit not functional to enable testing of the new duct smoke detector, also need to post updated points map at the RA, no access to the FACP room.
BLD11-01683 FIRE-Final Inspection9/8/20119/9/20119/9/2011 4:06:58 PMANR
Fire life safety final pending project related fire alarm permit final. Noted common restrooms are not finished. Remainder of life safety items including exit signs/EM lights, fire extinguishers, building address, and door hardware appear acceptable.
FIR08-00239 INSP-Sprinkler Rough-in9/8/20119/9/20119/9/2011 4:03:14 PMAPART
Pendent heads at the 2nd, 3rd and 4th floor corridors of building three approved for cover.