FIR10-00033
| INSP-Final Inspection | 9/8/2011 | 9/9/2011 | 9/9/2011 12:00:00 AM | A | FAIL |
|
|
Functionality of the recall and shunt trip functions passed, however the combination smoke/heat device at the top of the elevator shaft was located closer than 3' from the supply/return register and further than 2' from the sprinkler head, therefore it needs to be relocated. Also there is no fireman's hat light in the elevator, however there is an indicator light that remains solid regardless of the detector actuated. I let Colton know that if they can provide something in writing from the elevator contractor stating that the light is incapable of being made to flash that it would be acceptable due to the age of the elevator.
|