MEC13-03621
| Final | 9/5/2013 | 9/9/2013 | 9/9/2013 3:48:51 PM | P | NR |
|
|
as late as possible cody installer ###-#### Phone #: ###-#### >> Inspection requested via web by Dustin Rich
|
MEC13-03631
| Final | 9/9/2013 | 9/9/2013 | 9/9/2013 3:47:22 PM | P | PASS |
|
|
Brian Shoecraft ###-#### or Jeff Creek ###-#### Phone #: ###-#### x0000 >> Inspection requested via web by Andrea Creek
|
MEC13-03234
| Rough-in | 9/9/2013 | 9/9/2013 | 9/9/2013 3:27:10 PM | P | FAIL |
|
|
Phone #: ###-#### >> Inspection requested via web by Dustin Rich supply ducts size installed does not match report, no duct blast test done
|
MEC13-03586
| Final | 9/9/2013 | 9/9/2013 | 9/9/2013 2:42:23 PM | P | FAIL |
|
|
Shawn Phone #: ###-#### need manual j done and add dryer, range, and exhaust fans to permit
|
MEC13-03014
| Final | 9/6/2013 | 9/9/2013 | 9/9/2013 12:02:05 PM | A | FAIL |
|
|
call ryan with questions Phone #: ###-#### >> Inspection requested via web by Nicholas Paige need the cable tie downs at the gas appliances under hood and shutoff valves for the fire pits outdoors.
|
MEC13-03384
| Rough-in | 9/6/2013 | 9/9/2013 | 9/9/2013 11:58:32 AM | A | FAIL |
|
|
JOB CONTACT IS JOSH MORRIS Phone #: ###-#### >> Inspection requested via web by ADAM WARR missing some hangers at the VAV boxes
|
MEC13-03134
| Final | 9/6/2013 | 9/9/2013 | 9/9/2013 10:01:27 AM | A | PASS |
|
|
Contact Tim with EKC ###-#### Phone #: ###-#### >> Inspection requested via web by Dan Flaherty
|