Inspections for the day of: Tuesday, September 9, 2014.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR14-00552 INSP-Sprinkler Rough-in/Hydro9/9/20149/9/20149/9/2014 3:32:56 PMPPASS
Undeground hydro test passed
FIR14-00471 INSP-Sprinkler Rough-in9/9/20149/9/20149/9/2014 2:58:03 PMPPASS
New piping rough-in passed. I noted that new combustible concealed spaces have been formed and will need addressed before approval for cover can be given.
FIR14-00579 INSP-Sprinkler Rough-in/Hydro9/9/20149/9/20149/9/2014 1:49:46 PMPPASS
Rough-in passed. Piping can be covered.
BLD14-00361 FIRE-Final Inspection9/9/20149/9/20149/9/2014 1:49:13 PMPPASS
Life safety passed
FIR14-00339 INSP-Sprinkler Rough-in9/9/20149/9/20149/9/2014 1:48:03 PMPPASS
24 hour air test started at 1:00 with 44 1/2 psi on the guage
FIR14-00354 INSP-Sprinkler Rough-in9/9/20149/9/20149/9/2014 11:44:58 AMPPASS
Canopy 2/3 rough-in passed. Plan modifications are needed due to pipe routing changes and supply piping to the heads.
FIR14-00418 INSP-Sprinkler Rough-in9/9/20149/9/20149/9/2014 11:41:00 AMPPASS
Rough-in passed. Tenting has not been completed. No piping can be covered.
FIR14-00416 INSP-Sprinkler Rough-in9/9/20149/9/20149/9/2014 11:39:27 AMPPASS
Rough-in and tenting passed. Piping can be covered.
BLD14-02425 FIRE-Final Inspection9/8/20149/9/20149/9/2014 11:26:16 AMAPART
Todays inspection was just for the smoke evac which passed
BLD14-02426 FIRE-Final Inspection9/8/20149/9/20149/9/2014 11:25:01 AMAPART
Todays inspection was just for the smoke evac which passed
FIR14-00339 INSP-Sprinkler Rough-in/Hydro9/8/20149/9/20149/9/2014 10:59:33 AMAPASS
Overhead hydro test for the canopy passed.
FIR14-00537 INSP-Sprinkler Rough-in/Hydro9/8/20149/9/20149/9/2014 10:28:22 AMAPASS
Overhead hydro tests passed for both systems.
FIR13-00697 INSP-Sprinkler Rough-in9/8/20149/9/20149/9/2014 9:53:50 AMAPASS
Don and I discussed two lights that are obstructions to the pendant sprinkler heads
BLD14-02610 FIRE-Final Inspection9/5/20149/9/20149/9/2014 9:52:58 AMAPASS
Life safety passed