Inspections for the day of: Wednesday, September 9, 2015.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD14-03302 FIRE-Final Inspection9/9/20159/9/20159/9/2015 2:47:19 PMPFAIL
Need city approved plans and small documents. I noted that the fire alarm panel in in a "trouble" condition, in-operative exit/emergency lighting and missing/expired fire extinguishers. Greg provided fire sprinkler plans that addressed the raising of the two overhead doors and the hydraulic calculations showed a design for "auto repair shop".
BLD15-01235 FIRE-Final Inspection9/4/20159/9/20159/9/2015 1:19:52 PMPPASS
Life safety passed. Previously listed items corrected
FIR15-00615 INSP-Final Inspection9/8/20159/9/20159/9/2015 12:20:33 PMAFAIL
No testing done since power has not been ran to the fire alarm equipment
FIR07-00819 FIR-Aging Inspection9/9/20159/9/20159/9/2015 10:33:27 AM NR
Jeff is going to follow up.
BLD15-02975 FIRE-Final Inspection9/8/20159/9/20159/9/2015 10:30:19 AMAPASS
Life safety passed
FIR07-00817 FIR-Aging Inspection9/9/20159/9/20159/9/2015 8:56:08 AM NR
Jeff is going to follow up.
BLD15-00312 FIRE-Final Inspection9/8/20159/9/20159/9/2015 8:31:29 AMAPASS
life safety passed
FIR15-00548 INSP-Sprinkler Rough-in9/8/20159/9/20159/9/2015 8:30:24 AMAPASS
Underground supply piping is ok to cover