Inspections for the day of: Friday, September 9, 2016.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD16-00266 FIRE-Final Inspection9/9/20169/9/20169/9/2016 1:09:16 PMPPASS
Previously noted items have been addressed/repaired, no modifications to fire sprinkler system, no fire alarms, fire extinguisher is in place and will have a current inspection tag. Final life fire safety inspection passed/complete.
FIR16-00305 INSP-Sprinkler Rough-in9/9/20169/9/20169/9/2016 12:52:57 PMPPASS
Rough to cover inspection for requested area's on level 1 west side complete, notated city approved drawings with pink highlighter area's inspected and approved for cover.
BLD16-03244 FIRE-Final Inspection9/8/20169/9/20169/9/2016 10:42:18 AMAPASS
No fire sprinklers, no fire alarms, fire extinguisher has current inspection tag and will be mounted in discussed location. Final life fire safety inspection passed/complete.
FIR16-00088 INSP-Sprinkler Rough-in/Hydro9/9/20169/9/20169/9/2016 10:24:09 AMAPASS
200 psi hydrostatic test complete for underground main supply.
BLD16-03215 FIRE-Final Inspection9/9/20169/9/20169/9/2016 10:17:19 AMAPASS
Final life fire safety inspection has been completed for BLD14-01868, this is the last remaining item for this permit to be finaled for life fire safety, final life fire safety inspection for this area of work passed/complete.
BLD14-01868 FIRE-Final Inspection9/8/20169/9/20169/9/2016 10:13:50 AMAPASS
Previously noted items have been addressed/repaired. Fire sprinkler inspection is complete, no modifications have been made to the fire alarm system, commercial hood fire suppression system as well as fire extinguisher has current inspection tags. Final life fire safety inspection passed/complete.
FIR15-00900 INSP-Supply line flush9/8/20169/9/20169/9/2016 9:46:01 AMAFAIL
Flush will need to be performed again, something is obstructing the flow, piping will need to be repaired and flush rescheduled.