Inspections for the day of: Monday, September 9, 2019.
Number of inspections: 19
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE16-00386 ELE-Aging Inspection9/9/20199/9/20199/11/2019 3:41:19 PM FAIL
Expired permit
ELE19-03372 Electrical Rough-In9/9/20199/9/20199/9/2019 4:47:29 PMPPASS
Phone #: ###-#### Inspection requested via web by Calvin Bohrer
Where addition meets existing garage there are open splices and loose wiring that shall be terminated in a box. Addition rough in ok cover.
ELE19-03372 Permanent Service9/9/20199/9/20199/9/2019 4:25:01 PMPPASS
Phone #: ###-#### Inspection requested via web by Calvin Bohrer p/s u/g n ok
ELE19-02550 Final9/9/20199/9/20199/9/2019 3:57:05 PMPFAIL
Phone #: ###-#### Inspection requested via web by Ryan Wilson
210.52(A)(2)(1)- Fixed cabinets with tops count as wall space. A receptacle outlet shall be installed with in 6' of each side of fireplace.
ELE19-03370 Electrical Rough-In9/9/20199/9/20199/9/2019 3:16:13 PMPPASS
We would like an electrical cover inspection for enclosed reconfigured restroom area! Call me if there are any questions, access is around to the back of the building which you can drive to at either end, door will be open! Phone #: ###-#### Inspection requested via web by Steven Meredith I missed note about driving to rear, manager not happy with me, sorry, how everdoor not marked or labelled. Bathrooms expansion and hallway walls and hardlids rough in ok cover.
ELE19-03281 Final9/6/20199/9/20199/9/2019 3:01:29 PMPPASS
Call Brodie with any questions @ ###-#### Phone #: ###-#### Inspection requested via web by William Salts
Used existing circuit, changed HVAC on roof. Final ok
ELE19-02213 Final9/6/20199/9/20199/9/2019 2:34:56 PMAPART
first 6 from the N // Kevin Phone #: ###-####
first thing in AM...rescheduled from Friday
107, 108, 207, 208, 307, 308 TCO ok
ELE19-03284 Electrical Rough-In9/6/20199/9/20199/9/2019 1:43:03 PMAPASS
Contact is Brian Prussia. Thanks! Phone #: ###-#### Inspection requested via web by BRS Permitting
Lisitng confirmed, rough in ok.
ELE19-02176 Final9/6/20199/9/20199/9/2019 1:35:16 PMACANC
Please call ahead 1 hour so we can have a escort set up.
Phil is the contact Phone #: ###-#### Inspection requested via web by Deb Ipsen.
Contact called and rescheduled for 9am 9/10/19. Inspection cancelled from web by: Deb Ipsen
ELE19-02664 Electrical Rough-In9/9/20199/9/20199/9/2019 1:18:15 PMPPASS
Phone #: ###-#### Inspection requested via web by PAUL PINNEY
Kitchen, dining, bathroom walls rough in ok cover
ELE19-03303 Final9/9/20199/9/20199/9/2019 12:51:02 PMPPASS
Final Inspection Phone #: ###-#### Inspection requested via web by Joseph Yergensen Final ok
ELE19-03303 Electrical Rough-In9/8/20199/9/20199/9/2019 12:50:37 PMAPASS
I will be on site at 8 am to meet with inspector. Will have materials on ground to verify UL listings and materials used. Thanks Phone #: ###-#### Inspection requested via web by Joseph Yergensen
Listings confirmed, rough in ok
ELE19-02866 Final9/6/20199/9/20199/9/2019 11:55:45 AMAPASS
Final for mini cell site
Contact Alex Ybarra
Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek Final ok
ELE19-02996 Final9/6/20199/9/20199/9/2019 11:38:23 AMAPASS
Final on kitchen remodel. Thank You Phone #: ###-#### Inspection requested via web by Steve Blackmer
Repainting all compliant at time of inspection. Final ok
ELE19-03348 Electrical Rough-In9/6/20199/9/20199/9/2019 10:51:14 AMAPASS
Please call Brandon with any questions or access issues. Phone #: ###-#### Inspection requested via web by Kevin Perez
Located in courts 4 and 5 building, bath located in North West corner. Walls and hardlid rough in ok cover
ELE19-03339 Final9/6/20199/9/20199/9/2019 10:16:29 AMANH
Phone #: ###-#### Inspection requested via web by Tyler Bowen
No answer at door, called contact informed need someone home or electrical contractor to meet on site to enter fenced back yard. Will reschedule when arranged.
ELE19-01927 Final9/8/20199/9/20199/9/2019 10:00:25 AMAFAIL
Temp final Phone #: ###-#### Inspection requested via web by Kerri Hamilton
210.8(B)- All 120 volt 15 or 20 amp receptacle outlets located within 6' of a sink shall have GFCI protection. Bar above sink.
210.71- Conference rm 238 sq.ft., required floor receptacle shall be located at least 6' from a wall. 314.25- All boxes shall have covers. Disposal receptacle not trimmed.
330.30- MC cable shall be secured with in 12" of a box and supports not to exceed 4 1/2'. Front entry MC in ceiling, MC in conference rm bench to receptacles.
OK to move furniture in where needed.
ELE19-03293 Final9/6/20199/9/20199/9/2019 9:24:06 AMAPASS
Phone #: ###-#### Inspection requested via web by Steven Ragan
As per Idaho Power request replacement of meter base and mast covered under permit ELE19-03345. Final ok
ELE19-03015 Electrical Rough-In9/6/20199/9/20199/9/2019 9:20:50 AMAPASS
ground // John Phone #: ###-####
Low voltage portion of walker duct has been damaged by concrete saw. This section has been abandoned but will be sealed with flex seal to prevent concrete slurry from entering.
Underslab of new coffee bar rough in ok cover