Inspections for the day of: Wednesday, March 25, 2020.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE20-00945 Rough-In Permanent Service3/25/20203/25/20203/25/2020 4:06:37 PMPPASS
Phone #: ###-#### Inspection requested via web by Eric Brown
Rough in ok cover p/s u/g n ok
ELE20-01069 Electrical Rough-In3/24/20203/25/20203/25/2020 3:17:39 PMPPASS
Phone #: ###-#### Inspection requested via web by Kerri Hamilton '
Wall rough in ok cover
ELE20-00123 Electrical Rough-In3/24/20203/25/20203/25/2020 2:53:56 PMPPASS
Phone #: ###-#### Inspection requested via web by Jeremy Cloud
Grid on perimeter and focus, conference rooms.
ELE19-03641 Final3/18/20203/25/20203/25/2020 11:13:48 AMACANC
on site contact is Jay Thompson @ ###-####. Phone #: ###-#### Inspection requested via web by Jim Noll
Spoke with Jim who stated he would reschedule in future when safe to do so.
ELE20-01065 Final3/24/20203/25/20203/25/2020 11:12:48 AMAFAIL
Final inspection please. Stay safe. Have a bless week! Phone #: ###-#### Inspection requested via web by Kyle Lott
Went to space noted, individual stated no work has been done since moving in in January. Recall with specific notes as to which outlets added and where.
ELE20-01005 Electrical Rough-In3/24/20203/25/20203/25/2020 11:10:56 AMAFAIL
Rough in please. Thank you. Have a bless day! Phone #: ###-#### Inspection requested via web by Kyle Lott
Not much info on scope of work, found lights on entry ramp which appear new. Unable to verify listing. Provide listing and complete scope of work.
ELE19-03884 Final3/24/20203/25/20203/25/2020 10:31:58 AMAFAIL
Final inspection please. Thank you. Have a bless day! Phone #: ###-#### Inspection requested via web by Kyle Lott
110.12(A)- Unused openings shall be closed by approved means. KOs in bell boxes in ceiling. 225.32- Seperate structures shall have a disconnecting means.
342.30- IMC shall be secured with in 3' of emerging from grade.
BCC 4-05-23- Underground to bike structure did not have an inspection.
ELE20-01047 Temporary Service3/23/20203/25/20203/25/2020 10:10:52 AMACANC
Added a sub panel for power on 2-spider box cords Phone #: ###-#### Inspection requested via web by BRAD BAKER
Walked for rear in alley, worker informed me asbestos being removed. Visible cloud of dust in alley. Due to health dangers I will not enter with visible dust around, recall when done with asbestos removal.
ELE19-04502 Electrical Rough-In3/25/20203/25/20203/25/2020 9:13:55 AMAPASS
Piping for L2 PT deck Phone #: ###-#### Inspection requested via web by Tom Betty
A set of stamped city approved set of prints on site, confirmed.
Conference for in floor boxes along rails located on level 2 of live works units, west wall, ok to be slightly over 6' from start of wall to receptacle as required by 210.52(A). Structural cables and rebar require a minimum clearance of non stuctural components.
Area noted level 2 PT deck pour rough in ok cover.
ELE20-00974 Permanent Service3/23/20203/25/20203/25/2020 12:00:00 AMPCANC
cancel per owner 3-24-2020 Ron Phone #: ###-####