Inspections for the day of: Monday, March 9, 2020.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-04918 Electrical Rough-In3/9/20203/9/20203/9/2020 3:55:34 PMPPASS
3rd floor North tower 4 units Phone #: ###-#### Inspection requested via web by Todd Hall Units L- 309, 310, 311, 312 rough in ok cover
ELE20-00802 Electrical Rough-In3/9/20203/9/20203/9/2020 3:28:02 PMPPASS
Corrections made and stamped set on job Please call with any questions Phone #: ###-#### Inspection requested via web by Rex Boyles
Stamped city approved set of prints on site.
Walls rough in ok cover.
ELE19-00929 Final3/9/20203/9/20203/9/2020 2:20:12 PMPFAIL
Nathan Phone #: ###-####
406.12- All receptacles located in a garage shall be tamper resistant type.
Instructed to have secure all receptacles to boxes and all covers installed, including panel cover. Owner left off for inspection.
ELE20-00778 Temporary Service3/9/20203/9/20203/9/2020 1:44:09 PMPCANC
Mariela - Temporary service panel for food truck on corner of five mile and Ustick. If questions call permit desk "Gabe" Phone #: ###-#### Needed permenant service and food shack rough in inspection, see rough in/ ps
ELE20-00778 Rough-In Permanent Service3/9/20203/9/20203/9/2020 1:43:26 PMPFAIL
Mariela - Temporary service panel for food truck on corner of five mile and Ustick. If questions call permit desk "Gabe" Phone #: ###-#### 230.62- Energized parts shall be guarded from accidental contact. Unable to locate panel cover. Not installed when I arrived.
334.12- NM cable shall not be installed in a wet location. Interior of a conduit installed in a wet location is a wet location.
ELE19-03015 Final3/9/20203/9/20203/9/2020 1:07:41 PMPPASS
Keegan Phone #: ###-#### Final ok
ELE19-04907 Final3/6/20203/9/20203/9/2020 10:16:30 AMACANC
Need final - please call Mike with any questions 208.283.9055 Phone #: ###-#### Inspection requested via web by Deb Morton Permit finaled 3-06-2020
ELE19-02646 Final3/6/20203/9/20203/9/2020 10:15:06 AMAPASS
Install wall sign reading Walla Walla Clothing. Hook into existing power. No changes made to the Primary Power Phone #: ###-#### Inspection requested via web by Ken Olsen Final ok
ELE19-04886 Final3/6/20203/9/20203/9/2020 9:46:21 AMAPASS
access: 2020 Phone #: ###-#### Inspection requested via web by David Nelson Stucco being completed, all complete at time of inspection. Final ok
ELE20-00802 Electrical Rough-In3/7/20203/9/20203/9/2020 9:23:26 AMAFAIL
r/I of new walls and cut in boxes. Please call in advance for access! Thanks Phone #: ###-#### Inspection requested via web by Rex Boyles
No city approved set of prints on site, unable to inspect until set present.
ELE20-00803 Rough-In Permanent Service3/8/20203/9/20203/9/2020 8:42:12 AMAPASS
Phone #: ###-#### Inspection requested via web by Neal Rumsey
Rough in ok cover p/s u/g n ok