ELE19-04513
| Electrical Rough-In | 4/27/2020 | 4/27/2020 | 4/27/2020 3:13:26 PM | P | PASS |
|
|
Level 5 garage. Deck pour C. Phone #: ###-#### Inspection requested via web by Stephanie Huston Pour noted rough in ok cover
|
ELE20-01356
| Electrical Rough-In | 4/27/2020 | 4/27/2020 | 4/27/2020 2:35:03 PM | P | PASS |
|
|
screened // Leon Phone #: ###-#### Contractor to terminate all grounded conductors in individual terminals, landed with grounding conductors at time of inspection as per 408.41. Main areas switching to be wireless, shall be installed and operational at time of final. Rough in ok cover p/s u/g n ok
|
ELE20-01423
| Rough-In Permanent Service | 4/27/2020 | 4/27/2020 | 4/27/2020 2:06:10 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Troy Ballard Underground to service not connected to service riser at time of inspection. Attic trimmed at rough in. Rough in ok cover. p/s u/g n ok
|
ELE20-00739
| Electrical Rough-In | 4/27/2020 | 4/27/2020 | 4/27/2020 1:07:01 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Laurie Hoelscher Listing confirmed and disconnecting means located on each of 3 LED drivers above ceiling in unit 460. Rough in ok cover.
|
ELE19-04197
| ELE-Request for Extension | 4/27/2020 | 4/27/2020 | 4/27/2020 12:41:04 PM | P | PASS |
|
|
Requesting for permit extension please Have a bless week! Phone #: ###-#### Inspection requested via web by Kyle Lott Extension OK
|
ELE20-01443
| Temporary Service | 4/27/2020 | 4/27/2020 | 4/27/2020 12:40:20 PM | P | CANC |
|
|
Overhead power pole Phone #: ###-#### Inspection requested via web by Dean Gernaat Address is not correct. Contractor will correct and recall.
|
ELE20-01232
| Final | 4/24/2020 | 4/27/2020 | 4/27/2020 11:35:05 AM | A | FAIL |
|
|
Hot tub has been completed, installed on 50 amp 2 pole breaker, 3-#6 , 1#10 pulled form panel to GFCI spa panel. #10 feeds to pumps and heaters, fence has been bonded back to tub with solid #8 ground. Side of yard is open, no fence, open access to inspect install of tub. Phone #: ###-#### Inspection requested via web by Kurt Carlson 314.20- All NM cables shall terminate in a box. BBQ receptacle wire installed in non-metallic flex laying on patio. BBQ walls not complete. 680.26- All non current carrying metal parts located wth in 5' horizontal and 12' vertical of hot tub shall be bonded to tub. Gutter. 680.42(B)- If edge of tub is less than 28" above surrounding surface an equipotential bond is required.
|
ELE20-01138
| Electrical Rough-In | 4/24/2020 | 4/27/2020 | 4/27/2020 10:25:23 AM | A | PASS |
|
|
Contact: Jeremy Thornock - wall rough-in please Phone #: ###-#### Inspection requested via web by Deb Gooden Additional walls rough in ok cover.
|
ELE20-00311
| Electrical Rough-In | 4/24/2020 | 4/27/2020 | 4/27/2020 9:15:07 AM | A | PASS |
|
|
In need of a rough-in inspection prior to cover. Please call Brenden with any issues. ###-#### Phone #: ###-#### Inspection requested via web by Joe McLean Show window receptacles and circuits not included on print, will be required as per 210.62. Wall rough in only ok cover
|
ELE20-01256
| Electrical Rough-In | 4/24/2020 | 4/27/2020 | 4/27/2020 8:43:17 AM | P | CANC |
|
|
It will be open. This is for a partial rough in. If you have any questions please feel free to contact Tony ###-####. Thanks!! Phone #: ###-#### >> Inspection requested via web by Clayton Morgan Inspection cancelled from web by: Clayton Morgan
|