Inspections for the day of: Monday, April 27, 2020.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-04513 Electrical Rough-In4/27/20204/27/20204/27/2020 3:13:26 PMPPASS
Level 5 garage. Deck pour C. Phone #: ###-#### Inspection requested via web by Stephanie Huston
Pour noted rough in ok cover
ELE20-01356 Electrical Rough-In4/27/20204/27/20204/27/2020 2:35:03 PMPPASS
screened // Leon Phone #: ###-####
Contractor to terminate all grounded conductors in individual terminals, landed with grounding conductors at time of inspection as per 408.41.
Main areas switching to be wireless, shall be installed and operational at time of final.
Rough in ok cover p/s u/g n ok
ELE20-01423 Rough-In Permanent Service4/27/20204/27/20204/27/2020 2:06:10 PMPPASS
Phone #: ###-#### Inspection requested via web by Troy Ballard
Underground to service not connected to service riser at time of inspection. Attic trimmed at rough in. Rough in ok cover. p/s u/g n ok
ELE20-00739 Electrical Rough-In4/27/20204/27/20204/27/2020 1:07:01 PMPPASS
Phone #: ###-#### Inspection requested via web by Laurie Hoelscher
Listing confirmed and disconnecting means located on each of 3 LED drivers above ceiling in unit 460. Rough in ok cover.
ELE19-04197 ELE-Request for Extension4/27/20204/27/20204/27/2020 12:41:04 PMPPASS
Requesting for permit extension please Have a bless week! Phone #: ###-#### Inspection requested via web by Kyle Lott
Extension OK
ELE20-01443 Temporary Service4/27/20204/27/20204/27/2020 12:40:20 PMPCANC
Overhead power pole Phone #: ###-#### Inspection requested via web by Dean Gernaat Address is not correct. Contractor will correct and recall.
ELE20-01232 Final4/24/20204/27/20204/27/2020 11:35:05 AMAFAIL
Hot tub has been completed, installed on 50 amp 2 pole breaker, 3-#6 , 1#10 pulled form panel to GFCI spa panel. #10 feeds to pumps and heaters, fence has been bonded back to tub with solid #8 ground. Side of yard is open, no fence, open access to inspect install of tub. Phone #: ###-#### Inspection requested via web by Kurt Carlson
314.20- All NM cables shall terminate in a box. BBQ receptacle wire installed in non-metallic flex laying on patio. BBQ walls not complete.
680.26- All non current carrying metal parts located wth in 5' horizontal and 12' vertical of hot tub shall be bonded to tub. Gutter.
680.42(B)- If edge of tub is less than 28" above surrounding surface an equipotential bond is required.
ELE20-01138 Electrical Rough-In4/24/20204/27/20204/27/2020 10:25:23 AMAPASS
Contact: Jeremy Thornock - wall rough-in please Phone #: ###-#### Inspection requested via web by Deb Gooden
Additional walls rough in ok cover.
ELE20-00311 Electrical Rough-In4/24/20204/27/20204/27/2020 9:15:07 AMAPASS
In need of a rough-in inspection prior to cover. Please call Brenden with any issues. ###-#### Phone #: ###-#### Inspection requested via web by Joe McLean
Show window receptacles and circuits not included on print, will be required as per 210.62. Wall rough in only ok cover
ELE20-01256 Electrical Rough-In4/24/20204/27/20204/27/2020 8:43:17 AMPCANC
It will be open. This is for a partial rough in. If you have any questions please feel free to contact Tony ###-####. Thanks!! Phone #: ###-#### >> Inspection requested via web by Clayton Morgan Inspection cancelled from web by: Clayton Morgan