Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE20-01507 Final5/1/20205/1/20205/1/2020 11:30:23 AMPPASS
Please call Garrett at ###-#### 1/2 hour prior to arrival. Thank you! Phone #: ###-#### Inspection requested via web by Lynn Proctor
Rough in completed under ELE20-00408.
Final ok
ELE20-00408 Final4/30/20205/1/20205/1/2020 11:27:39 AMAPASS
Please contact Garrett at ###-#### 1/2 hour prior to being there for the inspection. Phone #: ###-#### Inspection requested via web by Lynn Proctor Final ok
ELE20-01255 Rough-In Permanent Service4/30/20205/1/20205/1/2020 10:39:59 AMAFAIL
It is open. If you have any questions please feel free to contact Chaz ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan
110.3- As per manufacturers instructions, 80 to 125 amp breakers shall be installed at lowest position on bus bar, space 125 amp breaker is installed is rated at 50 amp max.
On main level living room recessed can cover shall be completely installed.
210,52(A)- A receptacle outlet shall be located with in 6' of basement bathroom door.
250.32(A)- A grounding electrode system shall be installed at seperate structures, house.
ELE20-01461 Temporary Service4/30/20205/1/20205/1/2020 9:25:37 AMAPASS
Jeff is the site contact. Thank you! Phone #: ###-#### Inspection requested via web by Stacie Tasker
Located around south end by southwest portable classroom. t/s u/g n ok