ELE17-04322
| ELE-Aging Inspection | 3/5/2020 | 3/5/2020 | 3/13/2020 1:58:39 PM | | DONE |
|
|
No activity. Call for inspection
|
ELE20-00484
| Temporary Service | 3/5/2020 | 3/5/2020 | 3/5/2020 2:47:36 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Alan Lusk t/s u/g n ok
|
ELE19-04228
| Electrical Rough-In | 3/5/2020 | 3/5/2020 | 3/5/2020 2:00:25 PM | P | PART |
|
|
Second floor, east side ceiling // Mark Phone #: ###-#### SE ceiling only ok to cover (Note: NE inspected and ready for cover once SOE cords and Transmission cable removed by others.)
|
ELE20-00761
| Final | 3/4/2020 | 3/5/2020 | 3/5/2020 1:22:01 PM | P | PASS |
|
|
Please call on way: Aleks ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks Final ok
|
ELE20-00761
| Electrical Rough-In | 3/5/2020 | 3/5/2020 | 3/5/2020 1:21:49 PM | P | PASS |
|
|
Please call on way: Aleks ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks Surface mounted conduit runs rough in ok
|
ELE19-04894
| Final | 3/5/2020 | 3/5/2020 | 3/5/2020 1:02:47 PM | P | PASS |
|
|
Please Call Luke prior to arrival Phone #: ###-#### Inspection requested via web by Kevin Perez House re-plugged and switched final ok
|
ELE20-00694
| Permanent Service | 3/2/2020 | 3/5/2020 | 3/5/2020 12:33:52 PM | P | PASS |
|
|
There will be guys there working. If you have any questions please feel free to contact Tony ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan Existing grounding can not be verified. Was told either UFER or plumbing. Asked for 2 ground rods as they could not confirm. Panel was also not securly attached to brick. Asked for anchors to be install prior to final. Service equipment is existing. Went from OH to UG. p/s u/g rec ok
|
ELE19-03509
| Final | 3/4/2020 | 3/5/2020 | 3/5/2020 11:15:06 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Jeremy Cloud 110.3 GFCI Hot grnd revers Elevator pit. GFCI dead SE Stair well door Exterior. Wall pack needs installed/repaired above main service. Pig tail needs install for sprinkler time clock. 440.24 Max overcurrent for 4 RTU's is 40A 45A installed. 330. MC Stapped Less than 1 1/4in from face of stud misc areas on exterior walls
|
ELE19-04505
| Electrical Rough-In | 3/4/2020 | 3/5/2020 | 3/5/2020 10:19:50 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Jeremy Cloud Underground covered prior to inspection. 2- 2in conduits crossing pavered parking area from main building to garage and 1 1in conduit crossing pavered area for parking lot lights. Ends had been left open to verify deapth.
|
ELE19-04112
| Electrical Rough-In | 3/4/2020 | 3/5/2020 | 3/5/2020 10:01:24 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Troy Ballard rough in ok p/s u/g n ok
|
ELE20-00777
| Electrical Rough-In | 3/4/2020 | 3/5/2020 | 3/5/2020 9:43:14 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Ryan Wake IT server room and restroom ok to cover
|