Inspections for the day of: Thursday, March 5, 2020.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJames Ady
TitleELE-INSPECTOR
Phone #914-4683
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-04322 ELE-Aging Inspection3/5/20203/5/20203/13/2020 1:58:39 PM DONE
No activity. Call for inspection
ELE20-00484 Temporary Service3/5/20203/5/20203/5/2020 2:47:36 PMPPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk t/s u/g n ok
ELE19-04228 Electrical Rough-In3/5/20203/5/20203/5/2020 2:00:25 PMPPART
Second floor, east side ceiling // Mark Phone #: ###-#### SE ceiling only ok to cover (Note: NE inspected and ready for cover once SOE cords and Transmission cable removed by others.)
ELE20-00761 Final3/4/20203/5/20203/5/2020 1:22:01 PMPPASS
Please call on way: Aleks ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks Final ok
ELE20-00761 Electrical Rough-In3/5/20203/5/20203/5/2020 1:21:49 PMPPASS
Please call on way: Aleks ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks Surface mounted conduit runs rough in ok
ELE19-04894 Final3/5/20203/5/20203/5/2020 1:02:47 PMPPASS
Please Call Luke prior to arrival Phone #: ###-#### Inspection requested via web by Kevin Perez House re-plugged and switched final ok
ELE20-00694 Permanent Service3/2/20203/5/20203/5/2020 12:33:52 PMPPASS
There will be guys there working. If you have any questions please feel free to contact Tony ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan Existing grounding can not be verified. Was told either UFER or plumbing. Asked for 2 ground rods as they could not confirm. Panel was also not securly attached to brick. Asked for anchors to be install prior to final. Service equipment is existing. Went from OH to UG. p/s u/g rec ok
ELE19-03509 Final3/4/20203/5/20203/5/2020 11:15:06 AMAFAIL
Phone #: ###-#### Inspection requested via web by Jeremy Cloud 110.3 GFCI Hot grnd revers Elevator pit. GFCI dead SE Stair well door Exterior. Wall pack needs installed/repaired above main service. Pig tail needs install for sprinkler time clock. 440.24 Max overcurrent for 4 RTU's is 40A 45A installed. 330. MC Stapped Less than 1 1/4in from face of stud misc areas on exterior walls
ELE19-04505 Electrical Rough-In3/4/20203/5/20203/5/2020 10:19:50 AMAPASS
Phone #: ###-#### Inspection requested via web by Jeremy Cloud Underground covered prior to inspection. 2- 2in conduits crossing pavered parking area from main building to garage and 1 1in conduit crossing pavered area for parking lot lights. Ends had been left open to verify deapth.
ELE19-04112 Electrical Rough-In3/4/20203/5/20203/5/2020 10:01:24 AMAPASS
Phone #: ###-#### Inspection requested via web by Troy Ballard rough in ok p/s u/g n ok
ELE20-00777 Electrical Rough-In3/4/20203/5/20203/5/2020 9:43:14 AMAPASS
Phone #: ###-#### Inspection requested via web by Ryan Wake IT server room and restroom ok to cover