Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-04228 Electrical Rough-In8/4/20208/4/20208/4/2020 2:11:33 PMPPASS
Screened- Mark Phone #: ###-#### Hard lids and wall rough in as marked and dated on contractor print. ok to cover
ELE20-01794 Electrical Rough-In8/4/20208/4/20208/4/2020 1:15:49 PMPPASS
2nd floor ceiling inspection for lighting clouds Phone #: ###-#### Inspection requested via web by Shane Lott "Cloud" area drop ceiling only ok to cover. Discussed partial final requirments. (All life safety items shall be completed)
ELE19-02250 Final8/4/20208/4/20208/4/2020 12:47:18 PMPPASS
Please call Chris to sign off for final. Thanks! Phone #: ###-#### Inspection requested via web by Rafael Castillo final ok
ELE20-01564 Final8/4/20208/4/20208/4/2020 12:46:58 PMPPASS
Remodel call about inspection type // David Phone #: ###-#### Final ok
ELE20-02723 Temporary Service8/3/20208/4/20208/4/2020 12:13:41 PMAPASS
Phone #: ###-#### Inspection requested via web by Ryan Wake t/s u/g n ok
ELE20-01356 Conference8/4/20208/4/20208/4/2020 11:09:13 AMPDONE
Screened-Marcelo Phone #: ###-#### Discussed requirments of final. All required lighting outlets shall be funtional. Ok to blank missing fictures as long as required outlet is functional.
ELE20-02731 Rough-In Permanent Service8/4/20208/4/20208/4/2020 10:53:50 AMPPASS
Phone #: ###-#### Inspection requested via web by Therrin Robertson rough in ok to cover p/s u/g n ok
ELE20-02732 Rough-In Permanent Service8/4/20208/4/20208/4/2020 10:52:51 AMPPASS
Phone #: ###-#### Inspection requested via web by Therrin Robertson rough in ok to cover p/s u/g n ok
ELE20-02663 Electrical Rough-In8/3/20208/4/20208/4/2020 10:26:40 AMAPASS
James *screened* Phone #: ###-#### Water bond in skimmer and corner bond only ok to cover
ELE20-02451 Rough-In Permanent Service8/4/20208/4/20208/4/2020 10:19:08 AMAPASS
Phone #: ###-#### Inspection requested via web by Troy Ballard rough in ok p/s u/g n ok
ELE19-01688 Electrical Rough-In8/3/20208/4/20208/4/2020 9:40:17 AMAPART
screened - service gear and transformers // Jamie Phone #: ###-#### Serfvice gear and transformers checked. Transformersok to cover, Waiting on Performance testing and AFCI rating.
ELE20-02497 Electrical Rough-In8/3/20208/4/20208/4/2020 8:48:50 AMAFAIL
walls only Phone #: ###-#### Inspection requested via web by Dave Brueggemann 11o.3B Insulated bushings shall be installed on MC a per instructions. 330.24 MC Bent to breaking point(Next to back door.) 300.4 MC shall not be secured within 1 1/4in from face of framing(Water heater and recep back office) 110.12 Opening shall be closed(Missing conduit or KO seal Hall 4 gang.) MC not completed to floor box junction point.