MEC20-02601
| DOC - Permit Finaled | 6/25/2020 | 6/25/2020 | 6/25/2020 3:38:14 PM | A | PASS |
|
|
final ok
|
MEC20-02601
| Pressure Test | 6/25/2020 | 6/25/2020 | 6/25/2020 3:37:19 PM | P | PASS |
|
|
Please call Mark at ###-#### prior to arrival if possible. Phone #: ###-#### Inspection requested via web by Andrea Grigsby- 20lb gas pass co ok
|
MEC19-04127
| Final | 6/24/2020 | 6/25/2020 | 6/25/2020 3:05:53 PM | P | PASS |
|
|
Contact Kurtis for access ###-#### Phone #: ###-#### Inspection requested via web by John Bertram- final ok
|
MEC20-02510
| Pressure Test | 6/22/2020 | 6/25/2020 | 6/25/2020 2:31:54 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Scott Wickstrom 1- lower pressure gas test needs max 30 lb gauge and test above 20 psi- test was at 10psi on a 60lb gauge- 2- need to install open tee between 2 gas valves in crawl 2417.1.4 2012 IRC when tying onto existing gas piping 3- provide co detector/s if none installed retest after corrections made
|
MEC19-04849
| Final | 6/25/2020 | 6/25/2020 | 6/25/2020 2:02:12 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Kristy Watson- final ok
|
MEC20-02550
| Final | 6/23/2020 | 6/25/2020 | 6/25/2020 1:39:19 PM | P | PASS |
|
|
Homeowner Justin Lloyd ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette- furnace a/c coil co locking caps ok
|
MEC20-02556
| Final | 6/24/2020 | 6/25/2020 | 6/25/2020 12:54:58 PM | P | PASS |
|
|
PLEASE CALL SANDRA THE HOMEOWNER WHEN IN ROUTE- ###-#### Phone #: ###-#### Inspection requested via web by Rick Montgomery- furnace a/c coil co locking caps ok
|
MEC20-02590
| Final | 6/25/2020 | 6/25/2020 | 6/25/2020 11:13:43 AM | A | PASS |
|
|
Antonio is the contact Phone #: ###-#### Inspection requested via web by stan lillquist- final 2 bath fans ok- no card onsite to sign
|
MEC20-02590
| Card not on site to sign | 6/25/2020 | 6/25/2020 | 6/25/2020 11:13:07 AM | A | PASS |
|
|
Antonio is the contact Phone #: ###-#### Inspection requested via web by stan lillquist- card not onsite
|
MEC20-02590
| Rough-in | 6/25/2020 | 6/25/2020 | 6/25/2020 11:12:39 AM | A | PASS |
|
|
Antonio is the contact Phone #: ###-#### Inspection requested via web by stan lillquist- R/I ok 2 bath fans ok
|
MIS20-00071
| MEC-Final | 6/24/2020 | 6/25/2020 | 6/25/2020 11:00:36 AM | A | DONE |
|
|
AN Phone #: ###-####- need shields installed on deep fat fryer- equipment under hood needs moved into working place with 6 inches from side of hood- grease filters need install in hood- rest is good- reschedule when ready
|
MEC20-01975
| Final | 6/23/2020 | 6/25/2020 | 6/25/2020 9:43:04 AM | A | PASS |
|
|
Please call when on the way. Thank you! Phone #: ###-#### Inspection requested via web by Denise Colin- furnace a/c coil co locking caps ok
|
MEC19-04849
| Final | 6/24/2020 | 6/25/2020 | 6/25/2020 9:03:50 AM | A | FAIL |
|
|
GARAGE CODE: 7060 Phone #: ###-#### Inspection requested via web by Kristy Watson- 1- need approved man j onsite 2- a/c needs locking caps on service ports 3- lineset needs to be off ground 3 and a half inches covered by landscaping rocks
|
MEC20-02315
| Rough-in | 6/24/2020 | 6/25/2020 | 6/25/2020 8:46:03 AM | A | PART |
|
|
duct seal inspection - cy Phone #: ###-#### Inspection requested via web by Brandon Sorensen- seal on duct ok- ok to insulate- need to call in another R/I when hood is in and ducting ran-
|
MEC19-05209
| Mec-Aging Inspection | 6/25/2020 | 6/25/2020 | 6/25/2020 7:52:55 AM | | CANC |
|
|
|
MEC19-05209
| DOC - Permit Finaled | 6/25/2020 | 6/25/2020 | 6/25/2020 7:52:29 AM | A | PASS |
|
|
|