Inspections for the day of: Monday, March 2, 2020.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorMark Moncarr
TitleELE-INSPECTOR
Phone #685-9023
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE20-00722 Temporary Service3/2/20203/2/20203/2/2020 2:14:09 PMPPASS
###-#### t/s u/g n ok
ELE20-00730 Conference3/2/20203/2/20203/2/2020 1:46:01 PMPDONE
Discussed service requirements and layout of house. Dedicated circuits. wall spacing etc. Homeowner has a grasp on what he is doing. Call me Tom with any questions.
ELE20-00730 Final3/2/20203/2/20203/2/2020 1:44:38 PMPCANC
Tyler Phone #: ###-#### Changed to a conference.
ELE17-02687 Final3/2/20203/2/20203/2/2020 1:20:26 PMPPASS
call for access Shawn Phone #: ###-#### Ok final.
ELE20-00073 Conference3/2/20203/2/20203/2/2020 12:29:39 PMPCANC
Tyler Phone #: ###-#### Called and left message with Bens elec, no return call. Name and number listed for contact says he doesnt know anything about this job.
ELE20-00721 Permanent Service3/1/20203/2/20203/2/2020 12:04:29 PMPPASS
call for access and to meet on site. Phone #: ###-#### Inspection requested via web by steve sellers Emergency service change. Service already energized. Upon final wires in conduit need to be changed to thhn
ELE20-00728 Final3/2/20203/2/20203/2/2020 11:56:38 AMPPASS
Homeowner will be on site as well as HVAC. Phone #: ###-#### Inspection requested via web by Arielle Hendricks Ok final. 30a max brkr installed.
ELE20-00722 Final3/2/20203/2/20203/2/2020 11:22:11 AMPCANC
Temp pole Phone #: ###-#### Inspection requested via web by Eric Brown Should have been t/s. I added a t/s.
ELE20-00716 Permanent Service2/28/20203/2/20203/2/2020 11:21:01 AMAPASS
Repair service - Idaho Power disconnected power. Phone #: ###-#### Inspection requested via web by Kendra Lanham No service work performed. New straps were needed for overhead. Already energized.
ELE20-00631 Final2/28/20203/2/20203/2/2020 10:43:58 AMAFAIL
Steven Phone #: ###-#### Line side connection is considered a second service. Minimum size service for residential is 60a. Wire needs changed from #10 to #6. I dont want main office number, I want the installers phone number.
ELE19-03302 Rough-In Permanent Service2/28/20203/2/20203/2/2020 9:57:59 AMAPASS
Hoping to get new service energized. Phone #: ###-#### Inspection requested via web by Rex Boyles Existing panel over stairs is just being re-fed. No circuits extending out. p/s o/h n ok
ELE20-00591 Rough-In Permanent Service2/28/20203/2/20203/2/2020 9:43:37 AMAPASS
Phone #: ###-#### Inspection requested via web by Rodney Monroe Ok cover p/s u/g n ok
ELE19-04800 Final3/1/20203/2/20203/2/2020 9:42:59 AMAPASS
Please call ahead Phone #: ###-#### Inspection requested via web by Kyle Dillon Ok final
ELE20-00321 Rough-In Permanent Service3/2/20203/2/20203/2/2020 9:14:18 AMAPASS
Please let me know if you have any questions. Thank you! Phone #: ###-#### Inspection requested via web by Dan Jennings Ok cover. p/s u/g n ok
ELE20-00723 Temporary Service3/2/20203/2/20203/2/2020 8:40:49 AMAPASS
Temp pole Phone #: ###-#### Inspection requested via web by Kevin Burke t/s o/h n ok