Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-01480 Electrical Rough-In2/4/20202/4/20202/4/2020 2:56:36 PMPPASS
Call with any questions, thanks! Phone #: ###-#### Inspection requested via web by Rachael Moore...
rough-in ok to cover
2 outlets needed added in spare bed and master bed....remove hall outlet off hall bath recep circuit
ELE20-00392 Electrical Rough-In2/3/20202/4/20202/4/2020 2:02:07 PMPPASS
Phone #: ###-#### Inspection requested via web by Kerri Hamilton...new office area walls and devising wall outlets...ok to cover
ELE19-03639 Electrical Rough-In2/4/20202/4/20202/4/2020 1:36:39 PMPPASS
3rd floor rough in Phone #: ###-#### Inspection requested via web by Todd Hall...

3rd floor units rough-in ok to cover
ELE20-00377 Permanent Service2/4/20202/4/20202/4/2020 12:27:46 PMPPASS
Should be ready to restore power early afternoon. Phone #: ###-#### Inspection requested via web by Dan Hilke...
p/s o/h reconnect ok
ELE19-04057 Electrical Rough-In2/4/20202/4/20202/4/2020 11:42:24 AMPCANC
Dirk Phone #: ###-####...required building permit needs pulled before inspection can be done
ELE19-03762 Final2/3/20202/4/20202/4/2020 11:16:57 AMAFAIL
Rocky Phone #: ###-####...labelling incomplete
ELE19-03762 Electrical Rough-In2/4/20202/4/20202/4/2020 11:16:33 AMAPASS
Rocky Phone #: ###-####...listings verified
ELE19-04924 Final2/3/20202/4/20202/4/2020 10:29:30 AMAPART
Partial final Phase 2 Phone #: ###-#### Inspection requested via web by David Feller...
Phase 2 of total project...new cubicle/work stations and breakroom...partial final for area
ELE19-01259 Electrical Rough-In2/3/20202/4/20202/4/2020 10:05:36 AMAPASS
Requesting 10:00 am inspection. Install 2 monument signs and three wall signs Phone #: ###-#### Inspection requested via web by Ken Olsen...disconnects and UL labels verified
ELE19-04055 Final2/4/20202/4/20202/4/2020 9:45:08 AMAPASS
final for service change...corrections made...ok to final
ELE19-04139 Final2/3/20202/4/20202/4/2020 9:44:34 AMAPASS
MAIN CONTACT - Levi Henry ###-#### Phone #: ###-#### Inspection requested via web by BRS Permitting....
labelling, disconnect, and OCPD ok
ELE19-04114 Final2/3/20202/4/20202/4/2020 9:24:29 AMAFAIL
Final inspection for Encore Townhomes. The garage door code is 6622. Please let me know if you have any questions. Thank you, Dan Phone #: ###-#### Inspection requested via web by Dan Jennings....
1) all exterior recepticles shall be rated weather resistant...406.9
2) plate for outlet under sink shall be rated to be used with handy box...110.3, 406.6
3) a recepticle shall be within 3ft of edge of each sink in master bathroom...210.52(D)
ELE19-04113 Final2/3/20202/4/20202/4/2020 9:24:02 AMAFAIL
Final inspection for Encore Townhomes. The garage door code is 6622, Please let me know if you have any question! Thank you, Dan Phone #: ###-#### Inspection requested via web by Dan Jennings....
1) all exterior recepticles shall be rated weather resistant...406.9
2) plate for outlet under sink shall be rated to be used with handy box...110.3, 406.6
3) a recepticle shall be within 3ft of edge of each sink in master bathroom...210.52(D)
ELE19-03892 Final2/3/20202/4/20202/4/2020 9:23:24 AMAFAIL
Final inspection for Encore Townhomes. The garage door code is 6622, Please let me know if you have any question! Thank you, Dan Phone #: ###-#### Inspection requested via web by Dan Jennings....
1) all exterior recepticles shall be rated weather resistant...406.9
2) plate for outlet under sink shall be rated to be used with handy box...110.3, 406.6
3) a recepticle shall be within 3ft of edge of each sink in master bathroom...210.52(D)
ELE19-03706 Final2/3/20202/4/20202/4/2020 9:22:41 AMAFAIL
Final inspection for Encore Townhomes. The garage door code is 6622, Please let me know if you have any question! Thank you, Dan Phone #: ###-#### Inspection requested via web by Dan Jennings.....
1) all exterior recepticles shall be rated weather resistant...406.9
2) plate for outlet under sink shall be rated to be used with handy box...110.3, 406.6
3) a recepticle shall be within 3ft of edge of each sink in master bathroom...210.52(D)