Inspections for the day of: Friday, March 20, 2020.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR19-00853 INSP-Final Inspection3/19/20203/20/20203/20/2020 2:56:22 PMACANC
Canceled per John.. Phone #: ###-#### Inspection requested via web by John Lopez
FIR19-00831 INSP-Sprinkler Rough-in3/19/20203/20/20203/20/2020 2:55:42 PMPPASS
The sprinkler piping in the high (tower) area is ok for cover.

Johnathon Phone #: ###-####
BLD20-00104 FIRE-Final Inspection3/20/20203/20/20203/20/2020 2:53:53 PMPPASS
Life safety passed.

Please call 30 minutes in advance Phone #: ###-#### Inspection requested via web by Chase Cheverton
FIR20-00070 INSP-Final Inspection3/20/20203/20/20203/20/2020 2:52:59 PMPPASS
Permit finaled.

Phone #: ###-#### Inspection requested via web by Sam Ball
FIR19-00933 INSP-Sprinkler Rough-in3/19/20203/20/20203/20/2020 10:41:57 AMAPASS
Rough-in passed for the overhead mains and piping. I need verification that "side sammys" can be used on the trusses. Piping in some of the hard lids is ok for cover as marked on the plans. Additional cover inspections will be needed when the remaining sprinkler drops have been installed.

Phone #: ###-#### Inspection requested via web by Sam Ball
BLD19-01594 FIRE-Final Inspection3/19/20203/20/20203/20/2020 9:41:13 AMAFAIL
Need project related fire alarm and fire sprinkler permits finaled, need all small documents. No inspection performed but we did conference on life safety items.

Bo Phone #: ###-####
FIR19-00954 INSP-Final Inspection3/19/20203/20/20203/20/2020 8:48:49 AMAFAIL
No inspection performed, need testing reports provided first, need elevator recall detectors mounted with-in 12" of deck, need means to test devices in the elevator shaft.

Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
FIR19-00845 INSP-Final Inspection3/19/20203/20/20203/20/2020 8:45:27 AMAFAIL
Need fees paid, need service tag on risers, need sticker on bell, need interconnect with the facp tested. Need above ground and underground test papers.

Contact is Zach Grasmick Phone #: ###-#### Inspection requested via web by Chris Green
FIR19-00655 INSP-Final Inspection3/19/20203/20/20203/20/2020 8:40:32 AMAPASS
Permit finaled.

Contact is Zach Grasmick, this inspection is for Underground as per Jim Page. Phone #: ###-#### Inspection requested via web by Chris Green
FIR20-00137 INSP-Final Inspection3/19/20203/20/20203/19/2020 3:03:37 PMACANC
ID DBS WILL BE ON SITE FOR FINAL ELEVATOR INSPECTION AND TESTING AT 08:30 IN THE MORNING.
REQUESTING AM INSPECTION TO TEST FIRE ALARM PORTION OF ADDED RECALL DEVICES. CALL MIKE KROLL ###-#### Phone #: ###-#### >> Inspection requested via web by StateFire Specialties Inspection cancelled from web by: StateFire Specialties