Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR20-00078 INSP-Conference4/1/20204/2/20204/2/2020 3:11:59 PMPDONE
Plan mods are needed showing the actual scope of work. Since this a panel replacement the entire system is required to meet current code. Notification devices are mounted too low and are missing in required locations. No actual testing was performed.

Phone #: ###-#### Inspection requested via web by Kristin Dolan
FIR19-00815 INSP-Sprinkler Rough-in4/1/20204/2/20204/2/2020 3:09:57 PMPFAIL
Provide plan mods indicating the actual pipe routing. Repair tenting. It appears the FDC needs to be relocated to the street side of the building. It is currently on the west side in the yard/land scaping.

Call James before heading out, rough and tenting inspection. Phone #: ###-#### Inspection requested via web by Anthony Minichiello
BLD20-00651 FIRE-Final Inspection3/24/20204/2/20204/2/2020 3:08:07 PMPPASS
Life safety passed.

Jon Phone #: ###-####
FIR20-00186 INSP-Sprinkler Rough-in4/1/20204/2/20204/2/2020 9:32:51 AMACANC
Tried to coordinate twice but it was not to be. Will need to be rescheduled.

Phone #: ###-#### Inspection requested via web by Connie Danes
BLD20-01108 FIRE-Final Inspection4/1/20204/2/20204/2/2020 9:32:15 AMPFAIL
Provide notification in the Conference room as discussed. Other life saftey items are ok.

Rachel Phone #: ###-####
FIR20-00074 INSP-Sprinkler Rough-in4/1/20204/2/20204/2/2020 9:31:02 AMAPASS
See the city approved plans for locations marked "ok" where piping is ok to cover.

Please call Jon with time frame. Phone #: ###-#### Inspection requested via web by Jeff Packham