Inspections for the day of: Thursday, April 23, 2020.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR19-00769 INSP-Sprinkler Rough-in/Hydro4/22/20204/23/20204/23/2020 2:30:56 PMPPASS
The rough-in passed for the piping mods. 200lb hydro test passed for the pipe mods.

Please give Jim Lewis a call to schedule the inspection time. ###-#### Phone #: ###-#### Inspection requested via web by Joshua Hansen
BLD20-00495 FIRE-Final Inspection4/23/20204/23/20204/23/2020 2:29:42 PMPFAIL
Provide sprinkler protection for the new room or remove ceiling as discussed, provide annual inspection tag for the fire extinguisher, remove the thumbturn deadbolt for the new room door, provide single action hardware on all interior doors as discussed. Screened-please call prior- 3 min away- Faith Phone #: ###-####
BLD20-00771 FIRE-Final Inspection4/21/20204/23/20204/23/2020 11:49:22 AMAPASS
Life safety passed.

Kyle Phone #: ###-####
FIR19-00783 INSP-Sprinkler Rough-in4/22/20204/23/20204/23/2020 8:38:16 AMACANC
Cancel per point of contact. Tanner **Cleared** Phone #: ###-####
BLD20-00656 FIRE-Final Inspection4/22/20204/23/20204/23/2020 8:11:32 AMAFAIL
Need to have the project related fire sprinkler permit finaled. Need to repair/rewire the new exit sign as discussed.

Lloyd Phone #: ###-####