Inspections for the day of: Tuesday, May 5, 2020.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR18-00629 INSP-Final Inspection5/1/20205/5/20205/6/2020 10:16:53 AMPCANC
please come after 2:30 if possible. this is for the forward flow for the new BFP. Phone #: ###-#### Inspection requested via web by Connie Danes
FIR19-00769 INSP-Sprinkler Rough-in5/4/20205/5/20205/5/2020 12:27:45 PMPPASS
The 24 hour air test was witnessed for both dry systems.

This Inspection will be to finish the 24-hour air test started on Monday afternoon. Please give Jim Lewis a call to schedule the inspection time. ###-#### Phone #: ###-#### Inspection requested via web by Joshua Hansen
BLD20-00298 FIRE-Final Inspection5/4/20205/5/20205/5/2020 10:28:28 AMPPASS
Life safety passed. See load reduction approved by the building and fire dept.



Jake Phone #: ###-####
FIR19-00783 INSP-Sprinkler Rough-in5/5/20205/5/20205/5/2020 10:06:31 AMPFAIL
Need as-builts showing the pipe routing changes and pipe size changes, repair the tenting in two spots, relocate one overspaced pendant in the breezeway and repir two hangers on the first floor.

screened // Tanner Phone #: ###-####
BLD20-00145 FIRE-Final Inspection5/4/20205/5/20205/5/2020 8:58:54 AMAPASS
Life safety passed. if you have any questions you can call me at ###-####

thanks
Mike Teeter Phone #: ###-#### Inspection requested via web by Mike Teeter
FIR19-00785 INSP-Final Inspection5/5/20205/5/20205/5/2020 12:00:00 AMPCANC
screened // Tanner Phone #: ###-####
BLD20-00298 FIRE-Final Inspection5/4/20205/5/20205/4/2020 11:19:02 AMPCANC
Jake Phone #: ###-####