BLD20-00725
| FIRE-Final Inspection | 7/31/2020 | 8/3/2020 | 8/3/2020 2:10:13 PM | A | CANC |
|
|
screened // Kyle Phone #: ###-####
|
BLD20-00308
| FIRE-Final Inspection | 7/31/2020 | 8/3/2020 | 8/3/2020 2:09:10 PM | A | FAIL |
|
|
Need the project related firer alarm and hood suppresion permits finaled. Need all small documents, need address, need the exit signs and emergency lights repaired, need verification the room/walls at the cooler/fire riser room is ok to delete.
screened // Kyle Phone #: ###-####
|
FIR20-00397
| INSP-Final Inspection | 8/3/2020 | 8/3/2020 | 8/3/2020 2:06:34 PM | P | FAIL |
|
|
Need to add notification due to the lower slatted/cloud fixtures in the Dinging area. They block the stobes. Need to show the duct smoke detector for the vanilla finish side. Plans need to be atleast submitted for me to issue a possible temp on the fire alarm and life safety. All items tested except for the notification and the duct smoke detectors.
Like to schedule at 3:30. Phone #: ###-#### Inspection requested via web by James Williams
|
FIR20-00033
| INSP-Final Inspection | 8/3/2020 | 8/3/2020 | 8/3/2020 2:03:55 PM | P | FAIL |
|
|
Tried twice but the test tank would not blow off nozzle caps. Will need to reschedule.
Phone #: 2084777315 >> Inspection requested via mobile web by Matt Robison
|
FIR20-00072
| INSP-Final Inspection | 8/3/2020 | 8/3/2020 | 8/3/2020 2:02:43 PM | P | PASS |
|
|
Permit finaled.
Phone #: ###-#### Inspection requested via web by Brian Carlisle
|
BLD20-01075
| FIRE-Conference | 8/3/2020 | 8/3/2020 | 8/3/2020 2:01:17 PM | P | DONE |
|
|
Contractor, engineer and myself discussed whether the canopies require interior sprinkler protection. I referenced the requirements of NFPA 13.
|
FIR20-00357
| INSP-Sprinkler Rough-in/Hydro | 7/30/2020 | 8/3/2020 | 8/3/2020 1:10:33 PM | P | PASS |
|
|
Overhead huydro witnessed with no pressure loss.
Contact Hayden Randolph ###-#### 30 min prior to Hydro Insp start please.
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
BLD19-03209
| FIRE-Final Inspection | 8/3/2020 | 8/3/2020 | 8/3/2020 1:07:46 PM | P | FAIL |
|
|
Inspection was for the remodeled restrooms. The new fire alarm notification system needs to be extended into this remodeled area.
screened // TOm Phone #: ###-####
|
BLD20-02525
| FIRE-Final Inspection | 8/3/2020 | 8/3/2020 | 8/3/2020 12:49:16 PM | P | PASS |
|
|
Life safety passed.
Screened- Mike Phone #: ###-####
|
FIR20-00033
| INSP-Final Inspection | 7/31/2020 | 8/3/2020 | 8/3/2020 10:43:20 AM | P | CANC |
|
|
Phone #: 2084777315 >> Inspection requested via mobile web by Matt Robison Inspection cancelled via mobile web on Monday, August 03, 2020.
|
FIR20-00385
| INSP-Final Inspection | 7/30/2020 | 8/3/2020 | 8/3/2020 10:34:26 AM | A | FAIL |
|
|
Functional test of suppression system witnessed. Will be ok to final when upgrade agreement is approved for the fire alarm system. Phone #: 2084777315 >> Inspection requested via mobile web by Matt Robison
|
FIR20-00384
| INSP-Final Inspection | 7/30/2020 | 8/3/2020 | 8/3/2020 10:34:03 AM | A | FAIL |
|
|
Functional test of suppression system witnessed. Will be ok to final when upgrade agreement is approved for the fire alarm system. Phone #: 2084777315 >> Inspection requested via mobile web by Matt Robison
|
FIR20-00492
| INSP-Sprinkler Rough-in | 8/3/2020 | 8/3/2020 | 8/3/2020 9:50:48 AM | P | PASS |
|
|
Rough-in passed. Piping can be covered. I noted and spoke to the fitter that if the back room is used for storage then the pendant heads are overspaced.
Phone #: ###-#### Inspection requested via web by Matthew Lewis
|
NAF20-00043
| INSP-Final | 7/29/2020 | 8/3/2020 | 8/3/2020 9:36:49 AM | A | FAIL |
|
|
Provide 18AH batteries, resubmit plans showing zone expander/power supply, clean up wiring, meet NEC for the interconnection between the FACP and the Zone Expander panel (exposed wire may need to be in conduit?). Please call 20-30 minutes prior to inspection. You will be meeting technician Jason Petty on site. Phone #: ###-#### Inspection requested via web by jason petty
|
FIR20-00453
| INSP-Final Inspection | 8/3/2020 | 8/3/2020 | 8/3/2020 9:14:50 AM | P | CANC |
|
|
Contact Andrew Larson ###-#### 30 min prior to Fire Final Insp start please he is requesting a NOON inspection time if at all possible please.
Thank YOU Phone #: ###-#### >> Inspection requested via web by Teri Cruickshank Inspection cancelled from web by: Teri Cruickshank
|
FIR19-00774
| INSP-Final Inspection | 7/31/2020 | 8/3/2020 | 8/3/2020 8:01:21 AM | A | PASS |
|
|
Permit finaled.
Tanner *screened* Phone #: ###-####
|