FIR14-00638
| INSP-Conference | 4/13/2015 | 4/13/2015 | 4/13/2015 3:25:34 PM | P | DONE |
|
|
Phone conversation regarding concealed spaces.
|
FIR14-00095
| INSP-Final Inspection | 4/13/2015 | 4/13/2015 | 4/13/2015 3:20:32 PM | P | PASS |
|
|
Remainder of fire alarm work completed. Inspection of flow and tamper switch pass. Fire Alarm Bell connection fixed on sight.
|
FIR14-00681
| INSP-Sprinkler Rough-in | 4/13/2015 | 4/13/2015 | 4/13/2015 2:34:28 PM | P | PART |
|
|
Inspection for cover at grid ceiling areas for wing D, first floor completed. Ok to cover. Noted three painted heads, misaligned branch and two sprinklers with wrong temperature rating.
|
FIR13-00723
| INSP-Sprinkler Rough-in/Hydro | 4/10/2015 | 4/13/2015 | 4/13/2015 11:48:55 AM | A | PASS |
|
|
Overhead hydrostatic test pass
|
FIR15-00170
| INSP-Sprinkler Rough-in | 4/10/2015 | 4/13/2015 | 4/13/2015 10:10:19 AM | A | PART |
|
|
Need City approved plans on site for verification of work completed. Consultation room and 12 new heads at new wall ok to cover. Noted missing coverage at existing electrical closet on north side and at southeast corner.
|
FIR14-00783
| INSP-Sprinkler Rough-in/Hydro | 4/10/2015 | 4/13/2015 | 4/13/2015 10:06:19 AM | A | NR |
|
|
Not ready per phone call with contractor.
|