FIR14-00638
| INSP-Sprinkler Rough-in | 4/16/2015 | 4/17/2015 | 4/17/2015 4:18:38 PM | A | CANC |
|
|
Wrong permit number requested for inspection. Inspection intended for overhead work not underground.
|
FIR14-00815
| INSP-Sprinkler Rough-in | 4/16/2015 | 4/17/2015 | 4/17/2015 4:08:14 PM | P | PART |
|
|
Part of dry system 1 rough in completed as marked on plans. Corrections items noted were missing head rm 400, missing hangar and head misaligned room 437, head misaligned rm 435 and remove comm cabling along hallway main. Verified draft stops per plan.
|
FIR15-00229
| INSP-Sprinkler Rough-in | 4/17/2015 | 4/17/2015 | 4/17/2015 2:33:20 PM | P | PART |
|
|
Ok to cover at new small officers per plan. Matched response heads to be provided throughout. Noted obstructed coverage at new breakroom, contractor to make adjustments to be verified at next inspection.
|
FIR14-00070
| INSP-Supply line flush | 4/17/2015 | 4/17/2015 | 4/17/2015 2:31:40 PM | P | CANC |
|
|
Cancelled by contractor.
|
FIR14-00071
| INSP-Supply line flush | 4/17/2015 | 4/17/2015 | 4/17/2015 2:30:22 PM | P | PART |
|
|
Underground flush completed satisfactory. Noted that there needs to be seisimic clearance between ductile riser and floor slab in bldg L.
|
BLD15-00537
| FIRE-Final Inspection | 4/16/2015 | 4/17/2015 | 4/17/2015 11:44:25 AM | A | PASS |
|
|
Life Safety Pass. All previous noted items complete satisfactory.
|
BLD14-03140
| FIRE-Final Inspection | 4/16/2015 | 4/17/2015 | 4/17/2015 11:22:11 AM | A | PART |
|
|
Fire Lifesafety pass for 2nd floor. Final pending finishes at first floor.
|
FIR15-00071
| INSP-Final Inspection | 4/16/2015 | 4/17/2015 | 4/17/2015 11:20:55 AM | A | PASS |
|
|
Scope of work completed. Final walk through completed, sprinkler pass. Sprinkler permit finaled.
|
FIR15-00069
| INSP-Final Inspection | 4/16/2015 | 4/17/2015 | 4/17/2015 11:20:31 AM | A | PASS |
|
|
Scope of work completed. Functional testing completed satisfactory, one device adjusted on site on first floor. Fire Alarm Permit Finaled.
|
FIR15-00170
| INSP-Final Inspection | 4/16/2015 | 4/17/2015 | 4/17/2015 9:53:06 AM | A | PASS |
|
|
Permit Finaled. Previously noticed items have been completed satisfactory. New drops in electrical closet and south east corner OK. Riser annual inspection due this month and scheduled for 4/17. No signature card on site.
|
BLD15-00009
| FIRE-Final Inspection | 4/16/2015 | 4/17/2015 | 4/17/2015 9:31:02 AM | A | FAIL |
|
|
Emergency exit/egress lighting not functional. Ceiling tiles to be replaced and electrical receptacles to be covered in new open tenant space.
|