FIR15-00125
| INSP-Sprinkler Rough-in | 4/17/2015 | 4/20/2015 | 4/20/2015 4:41:52 PM | P | FAIL |
|
|
Mixed response heads; new are quick, existing are standard. Replace so heads match response and temperature.
|
FIR14-00531
| INSP-Sprinkler Rough-in | 4/20/2015 | 4/20/2015 | 4/20/2015 4:40:27 PM | P | PART |
|
|
5th and 4th Floor corridors, tower 3 to fire doors OK to cover. Noticed one area in pod with missing hangar.
|
BLD15-00288
| FIRE-Final Inspection | 4/17/2015 | 4/20/2015 | 4/20/2015 4:39:31 PM | A | FAIL |
|
|
Emergency Exits signs not functioning. One exit sign to be relocated on non secure cipher door that leads into storage/warehouse. Three fire Extinguishers need to be hung.
|
NAF15-00001
| INSP-Supply line flush | 4/16/2015 | 4/20/2015 | 4/20/2015 1:19:32 PM | P | PART |
|
|
Underground supply flush completed satisfactory.
|
BLD15-00009
| FIRE-Final Inspection | 4/17/2015 | 4/20/2015 | 4/20/2015 11:44:50 AM | A | PASS |
|
|
Fire life safety passed. All previous noticed items have been satisfactory completed.
|
FIR14-00638
| INSP-Sprinkler Rough-in | 4/17/2015 | 4/20/2015 | 4/20/2015 11:22:41 AM | A | CANC |
|
|
Wrong permit number for intended inspection. Inspection for 3rd floor east wing not underground. Inspection completed under correct permit number.
|
BLD15-01099
| FIRE-Final Inspection | 4/17/2015 | 4/20/2015 | 4/20/2015 9:41:14 AM | A | FAIL |
|
|
Life safety correction to be made are as follows post bldg and suite number, post door to remain unlocked while space is occupied sign and remove/replace exit door hardware on main first and second floor exits to be single action.
|
FIR14-00638
| INSP-Sprinkler Rough-in/Hydro | 4/16/2015 | 4/20/2015 | 4/20/2015 9:12:35 AM | A | CANC |
|
|
Wrong permit number for intended inspection. Cancelled per conversation with contractor.
|