Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD13-02423 FIRE-Final Inspection8/15/20158/15/20158/15/2015 4:15:15 PMPPART
Test of exit signs and emergency lighting for new apartment building. A few emergency lights were added, and a few exit sings were repaired as needed. The parking garage emergency lighting was not tested due to the egress walking path not being indicated on the asphalt. An emergency light was added to the front lobby exit discharge, but this device is temporary. Other that that, exit signage and EM lights are OK.
Fire extinguishers and EVAC plans are installed.
There is still scaffolding in the center courtyard that will be removed prior to TCO.
FIR14-00890 INSP-Final Inspection8/15/20158/15/20158/15/2015 4:09:11 PMPPART
Fire alarm test for River's Edge Apts. All fire sprinkler systems (dry and wet), tested, including water flow, tampers, trip test of dry pipe valves, low air alarms, etc. All fire sprinkler systems tested satisfactorily. ested other initiating devices for elevator functions - recall, alt. recall shunt trip for both elevators. Elev. # 1 could not verify shunt trip - no access to heat detector. Tested MP, and other SDs for door holders, SFDs, etc.
Noted a circuit problem with unit sounders not sounding. Contractor agreed to troubleshoot before resuming testing.
NOTE: Parking garage notification not tested this visit.