Inspections for the day of: Sunday, August 16, 2015.
Number of inspections: 2
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorThomas Walsh
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD13-02423 FIRE-Final Inspection8/16/20158/16/20158/16/2015 11:30:35 AMPPART
Retest of emergency lighting to inspect problem units. All tested OK. Only emergency lighting not tested is parking garage, as egress path not painted yet.
Fire sprinkler and fire alarm testing is completed. 5th floor fire alarm system not fully tested - units not ready yet. Offsite monitoring in place.
Saffolding within aprking area still present - told this would be gone by Tuesday. Exterior scaffolding on the NW corner will remain, but should not affect egress or access to egress windows above.
Fire access road is not completed, and may not be done by the time they are requesting TCO. I mentioned that steel plating maybe required, but this would have to be approved by the FD. FD acess road is not signed or painted yet. Address on the front of the building is not yet installed.
Area of refuge comm. system not tested todate.
FIR14-00890 INSP-Alarm Testing8/16/20158/16/20158/16/2015 11:17:55 AMPPART
Continued testing of fire alarm system, following troubles encountered last inspection. Tested all floors general alarm and individual units for all floors - all tested satifactorily. Tested notification in parking garage - found two strobe units that were not operating. Tested 5th floor common areas - units not ready for testing.
Elevator #1 5th floor SDs, and HD not tested - problem with smoke guard unit. Dry pipe valves on the 5th floor need to be tested to confirm ext. bell is connected.
Confirmed off site monitoring and receipt of alarms - also proper address confirmed.
Fire alarm system is complete up to the 4th floor, except as noted above.