Inspections for the day of: Monday, August 17, 2015.
Number of inspections: 4
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorThomas Walsh
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR14-00598 INSP-Sprinkler Rough-in8/17/20158/17/20158/17/2015 3:53:14 PMPPART
Test of some hard lid areas in the basement of wings EF&G. See plans for areas inspected. OK to cover pipe in these areas.
FIR14-00890 INSP-Alarm Testing8/17/20158/17/20158/17/2015 3:17:10 PMPPART
Completion of fire alarm testing for floors P/G up to the 4th floor.
Tested two atic DP valves to ensure tied into exterior bell - OK
Tested Elevator # 1 recall, shunt trip, and activation of 5th floor smoke guard door - all tested OK. Retested two (2) strobe devices in P/G that did not work last test - tested OK
This test completes fire alarm system, up through the fourth floor.
FIR14-00430 INSP-Alarm Testing8/17/20158/17/20158/17/2015 3:10:11 PMPPART
Trip test of DP Valve for the north side of the parking garage. Ann accelerator was added to this system due to failure of last trip test.
Trip test past at 35 seconds to waterflow.
FIR14-00531 INSP-Sprinkler Rough-in/Hydro8/14/20158/17/20158/17/2015 3:07:48 PMPPART
Hydrotest of new standpipe added in Tower 4 - 200 psi @ 2 hours - PASSED