FIR14-00598
| INSP-Sprinkler Rough-in | 8/17/2015 | 8/17/2015 | 8/17/2015 3:53:14 PM | P | PART |
|
|
Test of some hard lid areas in the basement of wings EF&G. See plans for areas inspected. OK to cover pipe in these areas.
|
FIR14-00890
| INSP-Alarm Testing | 8/17/2015 | 8/17/2015 | 8/17/2015 3:17:10 PM | P | PART |
|
|
Completion of fire alarm testing for floors P/G up to the 4th floor. Tested two atic DP valves to ensure tied into exterior bell - OK Tested Elevator # 1 recall, shunt trip, and activation of 5th floor smoke guard door - all tested OK. Retested two (2) strobe devices in P/G that did not work last test - tested OK This test completes fire alarm system, up through the fourth floor.
|
FIR14-00430
| INSP-Alarm Testing | 8/17/2015 | 8/17/2015 | 8/17/2015 3:10:11 PM | P | PART |
|
|
Trip test of DP Valve for the north side of the parking garage. Ann accelerator was added to this system due to failure of last trip test. Trip test past at 35 seconds to waterflow.
|
FIR14-00531
| INSP-Sprinkler Rough-in/Hydro | 8/14/2015 | 8/17/2015 | 8/17/2015 3:07:48 PM | P | PART |
|
|
Hydrotest of new standpipe added in Tower 4 - 200 psi @ 2 hours - PASSED
|