Inspections for the day of: Monday, January 27, 2020.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD19-04158 FIRE-Final Inspection1/27/20201/27/20201/27/2020 2:46:38 PMACANC
Phone #: ###-#### Inspection requested via web by Todd Landvatter
FIR19-00516 INSP-Sprinkler Rough-in1/27/20201/27/20201/27/2020 2:44:35 PMPPART
Rough to cover inspection for overehad fire sprinkler piping located above level 1 parking garage hardlids complete, parking garage level 1 hardlids approved for cover. Rough to cover inspection for level 1 overhead fire sprinkler piping above hardlids on exterior canopy complete, exterior canopy with fire sprinkler piping approved for cover.

Tony Cetani is requesting a Rough to Cover on 1st Floor Dry Pendant Area in Garage.
Phone #: ###-#### Inspection requested via web by Stan Beus
FIR19-00960 INSP-Final Inspection1/27/20201/27/20201/27/2020 11:44:17 AMPPASS
Final fire alarm inspection for area of work complete.

Phone #: ###-#### Inspection requested via web by Sam Ball
BLD19-01970 FIRE-Final Inspection1/24/20201/27/20201/27/2020 9:41:18 AMAPASS
Previously noted items have been corrected, fnal life safety inspection complete, permit sign off card not available at time of inspection no signatures provided.


DO NOT RESCHEDULE WITH IF NOT GC CALLING Ryan Phone #: ###-####
BLD19-04158 FIRE-Final Inspection1/24/20201/27/20201/27/2020 8:27:37 AMAFAIL
Electromagnetically locked doors in lobby does not comply with 1010.1.9.9, note 1. Door needs to comply with 1010.1.9.8 due to the door being electrically locked, required criteria is listed under section 1010.1.9.8 of the 2015 IFC. Door hardware on hallway egress door to stairwell is to be changed to access controilled type hardware, city approved plans need to reflect hardware change, plans currently show hardware being existing.

Phone #: ###-#### Inspection requested via web by Todd Landvatter
BLD19-01427 FIRE-Final Inspection1/24/20201/27/20201/27/2020 8:14:48 AMAPASS
Hardware for door 418A has been approved per notes entered 23JAN2020 and will be free egress, not access controlled, final life fire safety inspection is complete.

Jon Phone #: ###-####