FIR19-00516
| INSP-Conference | 1/6/2020 | 1/6/2020 | 1/6/2020 3:27:48 PM | P | DONE |
|
|
Fire conference complete, discussed small changes to fire sprinkler main in parking garage routing by exit doors, main was shown directly in front of exit doors, minor changes to be made to get main farther way from doorway entry. Changes will be notated on the as-builts for items discussed today.
Tony Phone #: ###-####
|
BLD19-04226
| FIRE-Final Inspection | 1/3/2020 | 1/6/2020 | 1/6/2020 3:23:55 PM | P | FAIL |
|
|
Provide fire extinguisher with a current inspection tag and place in tenant space as discussed. Provide second peice for the fire sprinkler escutcheons that were missing.
Please call if you would like me to meet you. Thank you Michael McHargue ###-#### Phone #: ###-#### Inspection requested via web by Michael McHargue
|
FIR19-00489
| INSP-Sprinkler Rough-in | 1/3/2020 | 1/6/2020 | 1/6/2020 2:06:11 PM | P | PART |
|
|
Onsite city approved plans have been marked with red ink hardlids that are approved for cover.
Todd Ketterling is the contact for this RTC inspection. We appreciate your help. Thank you Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR19-00516
| INSP-Sprinkler Rough-in | 1/6/2020 | 1/6/2020 | 1/6/2020 12:15:02 PM | P | CANC |
|
|
Request was for a conference, this request is cancelled.
Tony Phone #: ###-####
|
BLD19-04131
| FIRE-Final Inspection | 1/2/2020 | 1/6/2020 | 1/6/2020 12:04:11 PM | A | PASS |
|
|
No fire alarm modifications, no fire sprinkler modifications, fire extinguishers are in common areas with current inspection tags. Final life fire safety inspection for TCO occupancy complete.
remi Phone #: ###-####
|
FIR19-00634
| INSP-Final Inspection | 1/3/2020 | 1/6/2020 | 1/6/2020 11:04:31 AM | P | CANC |
|
|
We would like this inspection at 1:00 pm. This is when the elevator company will be there along with the elevator inspector. Please call Nate at ###-#### with inspection time. Phone #: ###-#### >> Inspection requested via web by Lori Brungardt Inspection cancelled from web by: Lori Brungardt
|
FIR19-00638
| INSP-Final Inspection | 1/3/2020 | 1/6/2020 | 1/6/2020 8:20:13 AM | P | CANC |
|
|
Contact is Dirk. Phone #: ###-#### >> Inspection requested via web by Morgan Ahten Inspection cancelled from web by: Morgan Ahten
|