Inspections for the day of: Monday, January 6, 2020.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR19-00516 INSP-Conference1/6/20201/6/20201/6/2020 3:27:48 PMPDONE
Fire conference complete, discussed small changes to fire sprinkler main in parking garage routing by exit doors, main was shown directly in front of exit doors, minor changes to be made to get main farther way from doorway entry. Changes will be notated on the as-builts for items discussed today.

Tony Phone #: ###-####
BLD19-04226 FIRE-Final Inspection1/3/20201/6/20201/6/2020 3:23:55 PMPFAIL
Provide fire extinguisher with a current inspection tag and place in tenant space as discussed. Provide second peice for the fire sprinkler escutcheons that were missing.

Please call if you would like me to meet you. Thank you Michael McHargue ###-#### Phone #: ###-#### Inspection requested via web by Michael McHargue
FIR19-00489 INSP-Sprinkler Rough-in1/3/20201/6/20201/6/2020 2:06:11 PMPPART
Onsite city approved plans have been marked with red ink hardlids that are approved for cover.

Todd Ketterling is the contact for this RTC inspection. We appreciate your help. Thank you Phone #: ###-#### Inspection requested via web by Stan Beus
FIR19-00516 INSP-Sprinkler Rough-in1/6/20201/6/20201/6/2020 12:15:02 PMPCANC
Request was for a conference, this request is cancelled.

Tony Phone #: ###-####
BLD19-04131 FIRE-Final Inspection1/2/20201/6/20201/6/2020 12:04:11 PMAPASS
No fire alarm modifications, no fire sprinkler modifications, fire extinguishers are in common areas with current inspection tags. Final life fire safety inspection for TCO occupancy complete.

remi Phone #: ###-####
FIR19-00634 INSP-Final Inspection1/3/20201/6/20201/6/2020 11:04:31 AMPCANC
We would like this inspection at 1:00 pm. This is when the elevator company will be there along with the elevator inspector.
Please call Nate at ###-#### with inspection time. Phone #: ###-#### >> Inspection requested via web by Lori Brungardt Inspection cancelled from web by: Lori Brungardt
FIR19-00638 INSP-Final Inspection1/3/20201/6/20201/6/2020 8:20:13 AMPCANC
Contact is Dirk. Phone #: ###-#### >> Inspection requested via web by Morgan Ahten Inspection cancelled from web by: Morgan Ahten