Inspections for the day of: Monday, February 10, 2020.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD20-00233 FIRE-Final Inspection2/10/20202/10/20202/10/2020 4:08:05 PMPPASS
No fire sprinklers, no fire alarm, fire extinguishers placed in common area. Final life safety for permitted area completed signature provided on permit. GR

Daniel Phone #: ###-####
BLD20-00282 FIRE-Final Inspection2/7/20202/10/20202/10/2020 3:36:11 PMPPASS
No fire sprinkler modifications, no fire alarm modifcations, fire extinguishers are placed with current inspection tags. Exit sign by main entry and exit in SE storage area to be serviced before BLD inspection. Final life safety inspection for area of work complete and signature provided on sign off card. GR


Christina Phone #: ###-####
BLD20-00291 FIRE-Final Inspection2/10/20202/10/20202/10/2020 2:54:07 PMPPASS
No fire sprinklers, no fire alarms, fire extinguisher in place with current inspection tag. Final life safety inspection for area of work complete, signature provided on permit sign off card. GR

Call ahead // Josh Phone #: ###-####
BLD20-00284 FIRE-Final Inspection2/7/20202/10/20202/10/2020 2:34:36 PMPFAIL
Sprinkler head in restroom on repair floor is overspaced. Small corridor next to restroom on repair floor needs fire sprinkler protection provided as well as tank storage area. Provide annual inspection for fire sprinkler system, no current tag on riser. Verify reason for antifreeze loop control valve being shut off. GR


Christina Phone #: ###-####
BLD19-04653 FIRE-Final Inspection2/10/20202/10/20202/10/2020 1:49:27 PMPCANC
FIR permit for fire sprinkler modifications must be completed before life fire safety inspection can be committed. This inspection request is cancelled. Bruce Phone #: ###-####
BLD19-00843 FIRE-Final Inspection2/7/20202/10/20202/10/2020 1:45:07 PMAFAIL
Exit signage needs to match what was submitted on city approved drawings, provide code compliant hardware on NW exit door, riser room is not 1 hour fire rated due to multiple holes in wall, provide and install knox box. Mount fire extinguishers at max 48" to mechanism as discussed. Still need to verify emergency operation of all emergency lights. FIR permit for fire sprinklers must be finaled before life safety can be completed. GR


Phone #: ###-#### Inspection requested via web by Zach Carter
FIR19-00754 INSP-Final Inspection2/10/20202/10/20202/10/2020 1:41:17 PMPFAIL
Install flexible couplings on riser, main climbing floor. Provide calc sticker on riser. Raise insulation/insulation covering in lower ceiling area off of heads. Points of attachment for sway bracing need to match detail on city approved drawings, ie through bolts and double lumber.

George Jess is the contact. Thanks for all you do! Phone #: ###-#### Inspection requested via web by Stan Beus
FIR19-00923 INSP-Final Inspection2/10/20202/10/20202/10/2020 1:37:36 PMPPASS
Final fire alarm inspection passed per scope of work. GR

Contact is Dan. Phone #: ###-#### Inspection requested via web by Morgan Ahten
FIR19-00742 INSP-Sprinkler Rough-in2/10/20202/10/20202/10/2020 1:36:26 PMPPASS
Sprinkler head coverage corrections for prop type decoration obstructions has been corrected, approved for cover. As builts must be submitted and permit reissued before final inspection.

mike oswald Phone #: ###-#### Inspection requested via web by Brodie Stenquist
FIR19-00816 INSP-Sprinkler Rough-in2/10/20202/10/20202/10/2020 10:25:45 AMPCANC
Point of contact called before inspection stating the drawings on site were not approved and will reschedule. GR

Call before heading out, rough and tenting towers 1;2 Phone #: ###-#### Inspection requested via web by Anthony Minichiello
BLD20-00334 FIRE-Final Inspection2/7/20202/10/20202/10/2020 9:44:34 AMAPASS
No fire sprinklers, no fire alarms, fire extinguishers are places with current inspection tags. Final life fire safety inspection for area of work complete, signature provided on permit sign off card.

Jim Phone #: ###-####
BLD19-03981 FIRE-Final Inspection2/7/20202/10/20202/10/2020 9:15:06 AMAFAIL
Called point of contact provided, was instructed that space was not open. Drove to tenant space, door was locked. Space was occupied before inspection process has been completed.
GR
Christian Phone #: ###-####
FIR19-00819 INSP-Final Inspection2/10/20202/10/20202/10/2020 8:55:12 AMAPASS
Final fire sprinkler inspection for area work complete.
BLD19-02962 FIRE-Final Inspection2/7/20202/10/20202/10/2020 8:47:31 AMAFAIL
Verify emergency egress lighting on exterior is operational could not test at time of inspection, provide current egress plan as discussed with point of contact, approved drawings on site still showed kitchen exit sign above door. Provide maximum occupancy placard. GR
miles Phone #: ###-####