Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD19-03981 FIRE-Final Inspection2/10/20202/11/20202/11/2020 2:21:05 PMPFAIL
Fire alarm/smoke detector system has been installed without an FIR permit, non required fire alarm/smoke detection system must comply with 2015 IFC, section 901.4.2, FIR permit has not been issued for fire alarm system, a FIR permit is required for all commercial fire alarm system installs. Door hardware on south door is not code compliant, no other items inspected.

Christian Phone #: ###-####
BLD19-02645 FIRE-Final Inspection2/10/20202/11/20202/11/2020 11:45:38 AMAFAIL
According to city approved drawings the new the new HVAC roof top untis are 3900 CFM each, HVAC units that are more than 2000 CFM requires unit shutdown on in-duct smoke detector activation. A seperate FIR perit will be required for any and all additions/modifications to the fire alarm system, no other items have been inspected.

Mike Phone #: ###-####
BLD19-03715 FIRE-Final Inspection2/10/20202/11/20202/11/2020 10:40:45 AMAPASS
No fire sprinklers, no fire alarms, no hood suppression system, fire extinguishers are placed with current inspection tags. Final life fire safety inspection is complete, signatures provided on permit sign off card.

TJ Phone #: ###-####
BLD19-04213 FIRE-Final Inspection2/10/20202/11/20202/11/2020 10:22:20 AMAPASS
No fire sprinkler modifications, no fire alarm modifications, fire extinguishers are in common areas with current inspection tags. Final life fire safety inspection for area of work complete, signatures provided on permit sign off card.

Mark Phone #: ###-####
BLD19-04653 FIRE-Final Inspection2/11/20202/11/20202/11/2020 10:05:02 AMAPASS
Fire sprinkler inspection is complete, no fire alarm modifications, fire extinguishers are placed in common areas with current inspection tags. Final life fire safety inspection for area of work complete, signatures provided on permit sign off card.
FIR20-00034 INSP-Final Inspection2/10/20202/11/20202/11/2020 10:03:45 AMAPASS
Final fire sprinkler inspection for area of work complete.

rick fry Phone #: ###-#### Inspection requested via web by Brodie Stenquist
FIR19-00803 INSP-Final Inspection2/10/20202/11/20202/11/2020 9:05:26 AMACANC
Scheduled for wrong day, this request is cancelled.

Needs to be done at 7:00am Phone #: ###-#### Inspection requested via web by Sam Ball