FIR19-00516
| INSP-Sprinkler Rough-in/Hydro | 2/26/2020 | 2/27/2020 | 2/27/2020 3:14:25 PM | P | PART |
|
|
Hydrostatic tests for 1st floor garage, Precast stair tower standpipe and the Northeast stair tower standpipe have been witnessed, no pressure loss observed.
Tony Cetani will be the contact. he is needing a hydro first floor garage and Precast Stairs. Thanks for all you do! Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR19-00390
| INSP-Final Inspection | 2/26/2020 | 2/27/2020 | 2/27/2020 3:07:46 PM | P | PASS |
|
|
Final fire sprinkler inspection is complete.
We would like to schedule this in conjunction with the fire alarm inspection. Please call Jeff with time frame. Phone #: ###-#### Inspection requested via web by Jeff Packham
|
FIR19-00390
| INSP-Sprinkler Rough-in | 2/27/2020 | 2/27/2020 | 2/27/2020 2:29:33 PM | P | PASS |
|
|
Rough in inspection is complete.
We would like to complete this in conjunction with our other inspection today. Please call Troy with time frame or questions Phone #: ###-#### Inspection requested via web by Jeff Packham
|
FIR19-00755
| INSP-Final Inspection | 2/27/2020 | 2/27/2020 | 2/27/2020 2:28:46 PM | P | PASS |
|
|
Final fire sprinkler inspection is complete.
Contact Brandon Myers ###-#### 30 min prior to Final Inspection start please.
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
FIR19-00939
| INSP-Final Inspection | 2/25/2020 | 2/27/2020 | 2/27/2020 2:05:35 PM | P | FAIL |
|
|
Annunciator is installed in a different location than what is shown on the city approved drawings. Fire system is being monitored by internet, associated components for monitoring/emergency power need to be submitted and approved prior to final sign off.
Contact is Dan. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
FIR19-00148
| INSP-Final Inspection | 2/27/2020 | 2/27/2020 | 2/27/2020 11:03:23 AM | A | PASS |
|
|
Final inspection for underground supply complete.
|
FIR20-00094
| INSP-Final Inspection | 2/26/2020 | 2/27/2020 | 2/27/2020 10:58:27 AM | A | PASS |
|
|
Final fire sprinkler inspection for scope of work complete.
Phone #: ###-#### Inspection requested via web by Sam Ball
|
FIR20-00094
| INSP-Sprinkler Rough-in | 2/26/2020 | 2/27/2020 | 2/27/2020 10:57:45 AM | A | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping in area of work complete, approved for cover.
Phone #: ###-#### Inspection requested via web by Sam Ball
|
BLD18-01806
| FIRE-Final Inspection | 2/26/2020 | 2/27/2020 | 2/27/2020 9:36:55 AM | A | FAIL |
|
|
Speaker strobes in space are hanging by wires out of box. Provide 2 fire extinguishers with current inspection tags, one for the main level and one for the mezz. No fire sprinkler modifications are required.
Call for access- Nick Phone #: ###-####
|
BLD19-00248
| FIRE-Conference | 2/26/2020 | 2/27/2020 | 2/27/2020 9:36:54 AM | A | DONE |
|
|
Fire conferene complete.
Review new BSD occupancy and phasing schedule and requirements. Phone #: ###-#### Inspection requested via web by Chris Fuhrman
|
BLD20-00066
| FIRE-Final Inspection | 2/24/2020 | 2/27/2020 | 2/27/2020 7:21:09 AM | A | PASS |
|
|
Fire sprinkler inspection is complete, fire alarm inspection is complete, fire extinguishers are in common areas with current inspection tags. Final life fire safety inspection for area of work complete, signatures provided on permit sign off card.
Phone #: ###-#### Inspection requested via web by Chase Cheverton
|
BLD20-00065
| FIRE-Final Inspection | 2/24/2020 | 2/27/2020 | 2/27/2020 7:20:40 AM | A | PASS |
|
|
Fire sprinkler inspection is complete, fire alarm inspection is complete, fire extinguishers are in common areas with current inspection tags. Final life fire safety inspection for area of work complete, signatures provided on permit sign off card.
Phone #: ###-#### Inspection requested via web by Chase Cheverton
|
FIR20-00083
| INSP-Final Inspection | 2/24/2020 | 2/27/2020 | 2/27/2020 7:19:11 AM | A | PASS |
|
|
Final fire alarm inspection for area of work complete.
Needs to be done at 7:00 am Phone #: ###-#### Inspection requested via web by Sam Ball
|
FIR20-00082
| INSP-Final Inspection | 2/24/2020 | 2/27/2020 | 2/27/2020 7:18:36 AM | A | PASS |
|
|
Final fire alarm inspection for area of work complete.
Needs to be done at 7:00am Phone #: ###-#### Inspection requested via web by Sam Ball
|