Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR19-00845 INSP-Final Inspection3/11/20203/11/20203/11/2020 3:02:56 PMPFAIL
Exterior sidewall heads are to close to deck, minimum of 4 inches, not more than 6 inches from deck is the requirement for sidewalls per NFPA13.

Raul is contact Phone #: ###-#### Inspection requested via web by Chris Green
FIR19-00954 INSP-Final Inspection3/9/20203/11/20203/11/2020 3:01:50 PMPFAIL
Elevator was inop at time of inspection, elevator was out of service due to elevator inspection not being completed yet.

Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
FIR19-00845 INSP-Sprinkler Rough-in/Hydro3/11/20203/11/20203/11/2020 3:00:58 PMPDONE
Temporary heat was removed before temp heat was established. As discussed, if temp heat was removed and building reached below 40 degrees then a re-hydro will be required, re-hydor has been witnessed with no observed pressure loss at riser provided gauges.

Raul is contact Phone #: ###-#### Inspection requested via web by Chris Green
FIR20-00056 INSP-Conference3/9/20203/11/20203/11/2020 2:58:53 PMADONE
Fire conference complete.

Inspection requested via web by Ken Webster
FIR20-00063 INSP-Sprinkler Rough-in3/11/20203/11/20203/11/2020 11:41:41 AMPPART
Rough in inspection complete, piping between conditioned spaces approved for cover. No tenting installed at time of inspection, piping requiring tenting not approved for cover.

Tenting and overhead rough, call James before heading out. Phone #: ###-#### Inspection requested via web by Anthony Minichiello
BLD19-02691 FIRE-Final Inspection3/10/20203/11/20203/11/2020 11:26:28 AMAFAIL
Wall layout by breakroom area does not city approved drawings. Notated 2 areas that show exit sign/emergency lighting location but exit signs/emergency lighting are not in the city approved plan location. Provide exit discharge emergency illumination per note 12 on the building permit fire code review comments.

Back door lock box code is 1208 Phone #: ###-#### Inspection requested via web by Josh Strasser
FIR20-00075 INSP-Sprinkler Rough-in3/10/20203/11/20203/11/2020 10:55:51 AMAPASS
Previously noted item has been corrected, cover is approved, sticker placed approval.

Tenting inspection. Call Anthony before heading out. Thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
BLD19-01927 FIRE-Final Inspection3/10/20203/11/20203/11/2020 10:39:54 AMAFAIL
Could not test release function on north stairwell door due to wiring issue, will need to retest release after repair is made.

Test remote unlock switch for L5 stairwell doors. Phone #: ###-#### Inspection requested via web by Sam Reading
FIR19-00538 INSP-Final Inspection3/9/20203/11/20203/11/2020 10:38:55 AMAFAIL
Communicator battery trouble did not annunciate at the panel or report with monitoring.

Ken Pieron, Technician Phone #: ###-#### Inspection requested via web by John Siewert
FIR19-00537 INSP-Final Inspection3/9/20203/11/20203/11/2020 10:38:35 AMAFAIL
Communicator battery trouble did not annunciate at the panel or report with monitoring.

Ken Pieron, Technician Phone #: ###-#### Inspection requested via web by John Siewert
FIR19-00540 INSP-Final Inspection3/6/20203/11/20203/11/2020 10:16:17 AMAPASS
Final fire sprinkler inspection is complete.

Robert Chambers is the contact.Thanks! (: Phone #: ###-#### Inspection requested via web by Stan Beus
FIR19-00551 INSP-Final Inspection3/6/20203/11/20203/11/2020 10:15:13 AMAPASS
Final fire sprinkler inspection is complete.

Robert Chambers is the contact. Thanks! (: Phone #: ###-#### Inspection requested via web by Stan Beus