Inspections for the day of: Friday, March 20, 2020.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD19-03785 FIRE-Final Inspection3/19/20203/20/20203/20/2020 2:22:43 PMPPASS
Fire sprinkler inspection is complete, fire alarm inspection is complete, fire extinguishers are in common areas with current inspection tags. Final life fire safety inspection for area of work complete, signature card no available at time of inspection.

Fire life safety inspection after final inspection on FIR19-00862 Phone #: ###-#### Inspection requested via web by Jerry Jones
FIR19-00675 INSP-Final Inspection3/19/20203/20/20203/20/2020 2:21:28 PMPPASS
Final fire sprinkler inspection for scope of work is complete.

Please Call Steve Johnson upon arrival to B26 for escort Phone #: ###-#### Inspection requested via web by Steve Johnson
FIR20-00016 INSP-Sprinkler Rough-in/Hydro3/20/20203/20/20203/20/2020 2:20:42 PMPDONE
Hydrostatic test witnessed for area of work, no pressure loss observed.
FIR19-00862 INSP-Final Inspection3/19/20203/20/20203/20/2020 2:20:03 PMPPASS
Final fire sprinkler inspection for scope of work is complete.

Please Call Steve Johnson when you arrive in B26 Lobby to escort to areas. Phone #: ###-#### Inspection requested via web by Steve Johnson
FIR20-00111 INSP-Sprinkler Rough-in/Hydro3/19/20203/20/20203/20/2020 2:18:18 PMPPART
City approved plans have been notated with green highlighter areas approved for cover.

Austin Farnworth is the contact. The inspection will be for the 1st floor. Thanks! (: Phone #: ###-#### Inspection requested via web by Stan Beus
BLD19-01250 FIRE-Final Inspection3/20/20203/20/20203/20/2020 2:01:26 PMPPART
Final life fire safety inspection for TCO phase 1 is complete.

BLD19-04670 FIRE-Conference3/20/20203/20/20203/20/2020 1:18:34 PMPDONE
Fire conference is complete, large HVAC unit is 4000CFM according to the HVAC contractor. HVAC untis that 2001CFM and higher requires smoke detection for HVAC unit shutdown with remote annunciator. A seperate FIR permit is required for smoke detector install.

Johnathon Phone #: ###-####
FIR20-00122 INSP-Sprinkler Rough-in3/19/20203/20/20203/20/2020 12:18:09 PMPFAIL
Open outlet above finish ceiling with no sprinkler drop, area was notated on city approved drawings. No tenting installed at time of inspection.

Johnathon Phone #: ###-####
FIR20-00109 INSP-Sprinkler Rough-in3/19/20203/20/20203/20/2020 12:07:26 PMPPART
Plans have been corrected. White sealant type compound has been applied to the electrical boxes, white sealant has come in contact with sprinkler piping section between level 1 and 2, need to have a letter submitted for compatability of sealant and CPVC or piping needs to be replaced. No tenting installed at time of inspection, cover is not approved.

Johnathon Phone #: ###-####
FIR20-00098 INSP-Sprinkler Rough-in3/19/20203/20/20203/20/2020 12:04:29 PMPFAIL
City approved drawings has been notated with red ink where a sprinkler head was not installed. No tenting install at time of inspection.

Johnathon Phone #: ###-####
FIR20-00178 INSP-Final Inspection3/20/20203/20/20203/20/2020 9:42:53 AMACANC
FIR20-00178 INSP-Final Inspection3/20/20203/20/20203/20/2020 9:42:23 AMPPASS
Final fire alarm inspection for scope of work is complete.
FIR20-00178 INSP-Alarm Testing3/18/20203/20/20203/20/2020 9:41:14 AMADONE
Alarm testing is complete.

Request 10:00 am inspection for 1 speaker strobe relocation testing. Phone #: ###-#### Inspection requested via web by Joseph ATS Facility Systems
FIR20-00065 INSP-Sprinkler Rough-in3/19/20203/20/20203/20/2020 8:13:04 AMAPASS
Previously noted items have been corrected, all tenting in place at time of inspection, cover is approved. Approval sticker has been placed.

Call James when heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
FIR20-00066 INSP-Sprinkler Rough-in3/19/20203/20/20203/20/2020 8:12:33 AMAPASS
Previously noted items have been corrected, all tenting in place at time of inspection, cover is approved. Approval sticker has been placed.

Call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
FIR19-00522 INSP-Final Inspection3/17/20203/20/20203/20/2020 7:32:26 AMAFAIL
Numerous walls have been added in one of the tenant spaces, TI is marked on city approved drawings. Wall layout affects audio visual coverage, floor plan must match approved drawings, inspection was stopped.

Needs to be done at 7:00am Phone #: ###-#### Inspection requested via web by Sam Ball