Inspections for the day of: Wednesday, March 25, 2020.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR19-00950 INSP-Sprinkler Rough-in3/24/20203/25/20203/25/2020 2:21:15 PMPPART
City approved drawings has been notated with red ink areas approved for cover.

Colin Phone #: ###-####
FIR19-00743 INSP-Sprinkler Rough-in3/24/20203/25/20203/25/2020 12:56:25 PMPFAIL
During attic sprinkler coverage inspection the walls between the classrooms did not go all of the way to the bottom of the deck, since attic inspection the walls between classrooms is covered to the deck, upright coverage along walls between class rooms is overspaced in numerous areas.

Contact Tanner Loomis ###-#### RTC Insp for Areas A ; B sides, please contact Tanner 30 min prior to RTC Insp start please.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
FIR20-00210 INSP-Final Inspection3/24/20203/25/20203/25/2020 11:04:19 AMPFAIL
In-duct detector is mounted on the exterior of the ductwork outside exposed to the elements, detector is outside of its listed environment, provide conditioning for duct detector.

Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
BLD19-01594 FIRE-Final Inspection3/23/20203/25/20203/25/2020 10:28:55 AMAFAIL
Fire sprinkler riser room is not 1 hour rated as required.

Bo Phone #: ###-####
FIR19-00845 INSP-Final Inspection3/23/20203/25/20203/25/2020 10:28:23 AMAPASS
Final fire sprinkler inspection is complete.

Contact is Zach Grasmick Phone #: ###-#### Inspection requested via web by Chris Green
FIR19-00954 INSP-Final Inspection3/24/20203/25/20203/25/2020 10:28:23 AMAPASS
Final fire alarm inspection is complete.

Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
FIR19-00954 INSP-Final Inspection3/24/20203/25/20203/24/2020 9:23:52 AMPCANC
Contact is Dirk. Phone #: ###-#### >> Inspection requested via web by Morgan Ahten Inspection cancelled from web by: Morgan Ahten