FIR19-00950
| INSP-Sprinkler Rough-in | 3/24/2020 | 3/25/2020 | 3/25/2020 2:21:15 PM | P | PART |
|
|
City approved drawings has been notated with red ink areas approved for cover.
Colin Phone #: ###-####
|
FIR19-00743
| INSP-Sprinkler Rough-in | 3/24/2020 | 3/25/2020 | 3/25/2020 12:56:25 PM | P | FAIL |
|
|
During attic sprinkler coverage inspection the walls between the classrooms did not go all of the way to the bottom of the deck, since attic inspection the walls between classrooms is covered to the deck, upright coverage along walls between class rooms is overspaced in numerous areas.
Contact Tanner Loomis ###-#### RTC Insp for Areas A ; B sides, please contact Tanner 30 min prior to RTC Insp start please.
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
FIR20-00210
| INSP-Final Inspection | 3/24/2020 | 3/25/2020 | 3/25/2020 11:04:19 AM | P | FAIL |
|
|
In-duct detector is mounted on the exterior of the ductwork outside exposed to the elements, detector is outside of its listed environment, provide conditioning for duct detector.
Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
BLD19-01594
| FIRE-Final Inspection | 3/23/2020 | 3/25/2020 | 3/25/2020 10:28:55 AM | A | FAIL |
|
|
Fire sprinkler riser room is not 1 hour rated as required.
Bo Phone #: ###-####
|
FIR19-00845
| INSP-Final Inspection | 3/23/2020 | 3/25/2020 | 3/25/2020 10:28:23 AM | A | PASS |
|
|
Final fire sprinkler inspection is complete.
Contact is Zach Grasmick Phone #: ###-#### Inspection requested via web by Chris Green
|
FIR19-00954
| INSP-Final Inspection | 3/24/2020 | 3/25/2020 | 3/25/2020 10:28:23 AM | A | PASS |
|
|
Final fire alarm inspection is complete.
Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
FIR19-00954
| INSP-Final Inspection | 3/24/2020 | 3/25/2020 | 3/24/2020 9:23:52 AM | P | CANC |
|
|
Contact is Dirk. Phone #: ###-#### >> Inspection requested via web by Morgan Ahten Inspection cancelled from web by: Morgan Ahten
|