Inspections for the day of: Tuesday, March 3, 2020.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR15-00002 FIR-Aging Inspection3/3/20203/3/20203/11/2020 10:15:48 AM CANC
FIR19-00516 INSP-Sprinkler Rough-in/Hydro3/3/20203/3/20203/3/2020 5:05:58 PMPDONE
Hydrostatic test for dry systems 2 thru 6 witnessed, no pressure loss observed. Hydrostatic test for parking garage dry systems complete.

Tony Cetani requesting a Hydro.
###-####

Thank you Phone #: ###-#### Inspection requested via web by Stan Beus
FIR19-00489 INSP-Sprinkler Rough-in3/3/20203/3/20203/3/2020 3:19:39 PMPPART
Overhead fire sprinkler piping in kitchen area approved for cover.

Aron Foster is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
FIR20-00111 INSP-Sprinkler Rough-in3/3/20203/3/20203/3/2020 1:50:42 PMPPART
City approved plans have been notated with green highlighter areas approved for cover.

Austin Farnworth is requesting a RTC on the 2nd floor.
###-####.

Thank you
Phone #: ###-#### Inspection requested via web by Stan Beus
FIR20-00088 INSP-Final Inspection3/2/20203/3/20203/3/2020 11:15:36 AMAPASS
Final fire sprinkler inspection for area of work is complete.

Please call Adam with time frame or questions. Phone #: ###-#### Inspection requested via web by Jeff Packham
BLD18-01391 FIRE-Final Inspection3/3/20203/3/20203/3/2020 11:15:01 AMPPASS
Official letter from a PE has been provided, final life fire safety inspection for scope of work complete.

###-#### is my contact number cell... Per Romeo this should be good to go since we have a stamped certification letter from the project PE. Inspection requested via web by Wayne Berry
BLD19-01927 FIRE-Final Inspection3/2/20203/3/20203/3/2020 9:45:56 AMACANC
Code exceptions done. Need final ok for c of o Phone #: ###-#### >> Inspection requested via web by Sam Reading Inspection cancelled from web by: Sam Reading
FIR19-00809 INSP-Sprinkler Rough-in3/3/20203/3/20203/3/2020 9:08:46 AMPPASS
Previously noted items have been corrected, approved for cover.

Phone #: ###-#### Inspection requested via web by jeremiah robison
FIR20-00064 INSP-Sprinkler Rough-in3/3/20203/3/20203/3/2020 8:21:03 AMACANC
Call Anthony before heading out. Rough to cover. Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello Inspection cancelled from web by: Anthony Minichiello
FIR19-00656 INSP-Final Inspection3/2/20203/3/20203/2/2020 2:49:53 PMAPASS
Re-submitted plans reflect what is installed, final fire alarm inspection is complete.

Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price