FIR20-00064
| INSP-Sprinkler Rough-in | 3/4/2020 | 3/4/2020 | 3/4/2020 5:12:33 PM | P | PART |
|
|
Rough in inspection is complete, piping between conditioned spaces approved for cover, tenting was not installed correctly in numerous areas, cover is not approved for piping that requires tenting.
Call Anthony before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
FIR19-00516
| INSP-Sprinkler Rough-in | 3/2/2020 | 3/4/2020 | 3/4/2020 5:11:32 PM | P | DONE |
|
|
Fire pump commissioning complete.
Tony Cetani is the contact for this inspection. He is requesting a fire pump start up. He would like it at the end of day if possible. We appreciate your help. Thank you. Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR20-00097
| INSP-Final Inspection | 3/3/2020 | 3/4/2020 | 3/4/2020 5:05:40 PM | P | PASS |
|
|
Final fire alarm inspection for scope of work complete.
Contact is Dan. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
BLD20-00509
| FIRE-Final Inspection | 3/4/2020 | 3/4/2020 | 3/4/2020 12:58:51 PM | P | PASS |
|
|
Previously noted items have been corrected, permenat sugnage will be installed when received for "Door to remain unlocked while occupied". Final life fire safety inspection is complete, signature provided on permit sign off card.
Steven Phone #: ###-####
|
FIR20-00075
| INSP-Sprinkler Rough-in | 3/4/2020 | 3/4/2020 | 3/4/2020 12:22:17 PM | P | FAIL |
|
|
Minimum R38 not met at time of install.
As Built approved and insulation complete. Call Anthony before heading out, thank you! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
FIR19-00516
| INSP-Sprinkler Rough-in/Hydro | 3/4/2020 | 3/4/2020 | 3/4/2020 11:59:41 AM | P | PART |
|
|
24 hour air test started at 12PM with 41 PSI on all dry systems.
|
FIR19-00516
| INSP-Conference | 3/4/2020 | 3/4/2020 | 3/4/2020 11:58:26 AM | P | CANC |
|
|
Tony Cetani is the contact, this inspection is for a 24hr air test. Thanks for all the hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR19-00887
| INSP-Sprinkler Rough-in | 3/4/2020 | 3/4/2020 | 3/4/2020 11:57:36 AM | P | PASS |
|
|
Previously noted items have been corrected, approved for cover.
was told the insulation was fixed Phone #: ###-#### Inspection requested via web by jeremiah robison
|
BLD19-04789
| FIRE-Final Inspection | 2/25/2020 | 3/4/2020 | 3/4/2020 12:00:00 AM | A | CANC |
|
|
cancel per william
|