FIR20-00144
| INSP-Sprinkler Rough-in | 3/5/2020 | 3/5/2020 | 3/5/2020 3:25:52 PM | P | PART |
|
|
Rough to cover inspection for overhead fire sprinkler piping above hardlids complete, hardlids approved for cover.
Contact Tanner Loomis ###-#### 30 min prior to RTC Insp start please.
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
FIR20-00067
| INSP-Sprinkler Rough-in | 3/4/2020 | 3/5/2020 | 3/5/2020 3:24:35 PM | P | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping complete, approved for cover.
Tanner Phone #: ###-####
|
FIR20-00064
| INSP-Sprinkler Rough-in | 3/4/2020 | 3/5/2020 | 3/5/2020 2:35:11 PM | A | PASS |
|
|
Tenting corrections have been made, all tenting in place at time of inspection, cover is approved, sticker has been placed for approval.
Call Anthony before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
FIR19-00761
| INSP-Final Inspection | 3/4/2020 | 3/5/2020 | 3/5/2020 1:05:59 PM | A | CANC |
|
|
Rescheduled for 9AM, 06MAR2020, this request is cancelled.
Buck Phone #: ###-####
|
FIR19-00516
| INSP-Sprinkler Rough-in | 3/5/2020 | 3/5/2020 | 3/5/2020 1:05:17 PM | A | PART |
|
|
Rough in inspection for TCO phase 1 fire sprinkler piping is complete.
|
FIR19-00516
| INSP-Sprinkler Rough-in/Hydro | 3/5/2020 | 3/5/2020 | 3/5/2020 1:04:01 PM | P | DONE |
|
|
24 hour air test is complete.
|
FIR19-00516
| INSP-Final Inspection | 3/5/2020 | 3/5/2020 | 3/5/2020 1:02:40 PM | P | FAIL |
|
|
Temp heat in riser stairwell was not operational, gas was shut off, plastic sheeting does not cover entire opening, 40 degrees was not maintained as discussed, provide adequate freeze protection as discussed.
Tony Cetani is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
BLD19-03531
| FIRE-Final Inspection | 3/5/2020 | 3/5/2020 | 3/5/2020 9:20:56 AM | P | CANC |
|
|
Permit details shows signature not required for fire life safety, this request is cancelled, point of contact has been notified.
Craig Phone #: ###-####
|
FIR19-00935
| INSP-Final Inspection | 3/3/2020 | 3/5/2020 | 3/5/2020 7:42:04 AM | A | CANC |
|
|
Inspection request cancelled per conversation with point of contact due too trouble on the panel, inspection will be rescheduled for a later date.
Need inspection at 7 am, this is combined with chase towers. Phone #: ###-#### Inspection requested via web by Kristin Dolan
|