Inspections for the day of: Thursday, March 5, 2020.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR20-00144 INSP-Sprinkler Rough-in3/5/20203/5/20203/5/2020 3:25:52 PMPPART
Rough to cover inspection for overhead fire sprinkler piping above hardlids complete, hardlids approved for cover.

Contact Tanner Loomis ###-#### 30 min prior to RTC Insp start please.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
FIR20-00067 INSP-Sprinkler Rough-in3/4/20203/5/20203/5/2020 3:24:35 PMPPASS
Rough to cover inspection for overhead fire sprinkler piping complete, approved for cover.

Tanner Phone #: ###-####
FIR20-00064 INSP-Sprinkler Rough-in3/4/20203/5/20203/5/2020 2:35:11 PMAPASS
Tenting corrections have been made, all tenting in place at time of inspection, cover is approved, sticker has been placed for approval.

Call Anthony before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
FIR19-00761 INSP-Final Inspection3/4/20203/5/20203/5/2020 1:05:59 PMACANC
Rescheduled for 9AM, 06MAR2020, this request is cancelled.

Buck Phone #: ###-####
FIR19-00516 INSP-Sprinkler Rough-in3/5/20203/5/20203/5/2020 1:05:17 PMAPART
Rough in inspection for TCO phase 1 fire sprinkler piping is complete.
FIR19-00516 INSP-Sprinkler Rough-in/Hydro3/5/20203/5/20203/5/2020 1:04:01 PMPDONE
24 hour air test is complete.
FIR19-00516 INSP-Final Inspection3/5/20203/5/20203/5/2020 1:02:40 PMPFAIL
Temp heat in riser stairwell was not operational, gas was shut off, plastic sheeting does not cover entire opening, 40 degrees was not maintained as discussed, provide adequate freeze protection as discussed.

Tony Cetani is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
BLD19-03531 FIRE-Final Inspection3/5/20203/5/20203/5/2020 9:20:56 AMPCANC
Permit details shows signature not required for fire life safety, this request is cancelled, point of contact has been notified.

Craig Phone #: ###-####
FIR19-00935 INSP-Final Inspection3/3/20203/5/20203/5/2020 7:42:04 AMACANC
Inspection request cancelled per conversation with point of contact due too trouble on the panel, inspection will be rescheduled for a later date.

Need inspection at 7 am, this is combined with chase towers. Phone #: ###-#### Inspection requested via web by Kristin Dolan