Inspections for the day of: Monday, April 13, 2020.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR20-00255 INSP-Final Inspection4/10/20204/13/20204/13/2020 5:47:25 PMAPASS
Final inspection for AES communicator is complete. Reference letter submitted under FIR18-00329 for AES in existing school.

Please call Nate at ###-#### Phone #: ###-#### Inspection requested via web by Lori Brungardt
FIR20-00138 INSP-Sprinkler Rough-in4/10/20204/13/20204/13/2020 5:06:28 PMPCANC
Did not physically go to inspection request site, area of work is inside of an active hospital, located towards the center of the main building. Due to risk of exposure photo's were requested for the fire sprinkler rough in piping/sprinkler heads but none were recieved by the end of the business day, inspection request will need to be rescheduled, this request is cancelled.

Plans are on site Phone #: ###-#### Inspection requested via web by Sam Ball
BLD19-04633 FIRE-Conference4/13/20204/13/20204/13/2020 12:36:28 PMPDONE
Fire confernce is complete, atic heat detection will need to be revised before final inspection for acceptance, current drawing does not cover attic space correctly as discussed with Lee Meridith, Fire Alarm Plan Reviewer.

Tracey- conference Phone #: ###-####
FIR19-00630 INSP-Final Inspection4/10/20204/13/20204/13/2020 11:41:20 AMAFAIL
Provide mag lock release during general fire alarm for de-escalation room. Approved drawings will need to reflect the addition of the speaker/strobe added by kitchen hood instead of just speaker, a strobe needed to be added for proper visual coverage. CO2 detectors need to activate audio visual notification per alarm matrix. All other initiating devices have been tested without issues, hood reports to fire panel as required.

Buck - Screened for COVID 19 symptosm Phone #: ###-####
FIR20-00092 INSP-Final Inspection4/12/20204/13/20204/13/2020 11:37:47 AMAFAIL
Provide appliance shut-down on cafeteria side of cooking hood, appliances remained energized after hood activation. Modify hood drawing to show deletion of appliance nozzles as discussed.

Phone #: ###-#### Inspection requested via web by Don Kartchner
FIR19-00599 INSP-Final Inspection4/13/20204/13/20204/13/2020 11:32:14 AMPPART
Final fire sprinkler inspection is complete. Last remaining item to complete is the forward flow test, pitot tube not available at time of inspection.

Kenny Caldwell is the contact. The inspection is already being done this morning. Thanks (: Phone #: ###-#### Inspection requested via web by Stan Beus
FIR19-00365 INSP-Final Inspection4/10/20204/13/20204/13/2020 11:30:27 AMAPASS
Final inspection for underground supply is complete.

Kenny Caldwell is the contact. Have a good day (: Phone #: ###-#### Inspection requested via web by Stan Beus
FIR20-00062 INSP-Sprinkler Rough-in4/13/20204/13/20204/13/2020 11:29:23 AMPFAIL
Tenting has been altered by other trades in numerous areas, cover is not approved until tenting is corrected.

Tenting inspection, call James if issues. Phone #: ###-#### Inspection requested via web by Anthony Minichiello
FIR20-00061 INSP-Sprinkler Rough-in/Hydro4/13/20204/13/20204/13/2020 11:26:52 AMPFAIL
System lost 20psi during hydro. Tenting has been comprimised by other trades, cover is no longer autorized, a re-inspection for tenting is required. Cover sticker has been removed, any and all cover material installed before tenting re-inspection that prevents a visual inspection of the pipe will be required to be removed.
Hydro RE-inspection. Call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
FIR20-00140 INSP-Final Inspection4/10/20204/13/20204/13/2020 9:12:24 AMACANC
Gas meter was not placed, could not test gas shutdown on activation. Inspection will be rescheduled for a later date, this request is cancelled per conversation with point of contact.

Phone #: 2084777315 >> Inspection requested via mobile web by Matt Robison
BLD19-02706 FIRE-Final Inspection4/10/20204/13/20204/13/2020 8:27:14 AMAFAIL
As stated in the 25FEB2020 inspection notes, FIR permit for fire alarms must be completed and finaled before life fire safety will be completed.

Call ahead - Bill Phone #: ###-####