Inspections for the day of: Friday, April 3, 2020.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR20-00132 INSP-Sprinkler Rough-in4/1/20204/3/20204/3/2020 1:52:53 PMPPART
Rough in inspection complete, no tenting installed at time of inspection, cover is not approved.

Phone #: ###-#### Inspection requested via web by Jonathan Lee
FIR20-00125 INSP-Sprinkler Rough-in4/1/20204/3/20204/3/2020 1:52:39 PMPPART
Rough in inspection complete, no tenting installed at time of inspection, cover is not approved.

Phone #: ###-#### Inspection requested via web by Jonathan Lee
FIR19-00489 INSP-Sprinkler Rough-in/Hydro4/2/20204/3/20204/3/2020 1:52:01 PMADONE
Hydrostaic test for overhead fire sprinkler piping, levels 1 and 2 witnessed, no pressure loss observed.

Todd Ketterling is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
FIR20-00122 INSP-Sprinkler Rough-in4/1/20204/3/20204/3/2020 12:46:53 PMPFAIL
Plastic sheeting used for tenting, numerous areas where the pocket between sheetrock and piping is compromised.

Tenting Phone #: ###-#### Inspection requested via web by Jonathan Lee
FIR20-00108 INSP-Sprinkler Rough-in4/1/20204/3/20204/3/2020 12:41:27 PMPFAIL
Tenting not installed correctly in numerous areas, pocket between sheetrock and piping will be compromised, cover is not approved..

Tenting Phone #: ###-#### Inspection requested via web by Jonathan Lee
FIR19-00489 INSP-Final Inspection4/2/20204/3/20204/3/2020 12:25:54 PMACANC
Rescheduled for 06APR2020 per conversation with the GC and point of contact, sprinklers are ready to be made active but ceiling tiles missing in numerous areas. Per conversation with GC ceiling tiles should be in by the coordinated date, this requestb is cancelled.

Todd Ketterling is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
FIR20-00236 INSP-Final Inspection4/3/20204/3/20204/3/2020 12:10:24 PMPCANC
Rescheduled for 06APR2020 to coincide with fire alarm inspection. this request is cancelled per conversation with point of contact.

screened // Nate Phone #: ###-####
FIR19-00373 INSP-Final Inspection4/3/20204/3/20204/3/2020 10:18:49 AMAPASS
Final inspection for underground supply is complete.
FIR19-00373 INSP-Sprinkler Rough-in/Hydro4/3/20204/3/20204/3/2020 10:18:18 AMADONE
Underground hydrostatic test has been witnessed, no pressure loss was observed.
FIR19-00800 INSP-Final Inspection4/2/20204/3/20204/3/2020 8:48:33 AMPPASS
Plans have been updated showing upright heads being added, final fire sprinkler inspection for area of work is complete.

Cole Bierman is the contact. Thanks(: Phone #: ###-#### Inspection requested via web by Stan Beus
FIR19-00939 INSP-Final Inspection3/31/20204/3/20204/3/2020 8:36:54 AMAPART
Backup power for internet monitoring has been verified, plans still show annunciator inside of building instead of vestibule, permit can be finaled after plans show annunciator in its current location.

Contact is Dan. Phone #: ###-#### Inspection requested via web by Morgan Ahten
BLD19-04214 FIRE-Final Inspection4/2/20204/3/20204/3/2020 7:05:08 AMAFAIL
Install ceiling tiles in ares where sprinkler protection is complete, ceiling tiles were not installed in new conference room. Project has 2 attached FIR permits for fire sprinkler that will need to be finaled before life fire safety inspection can be signed off.

Call for access 30 mins- Shawn **stated they dont know anyone that is sick or has traveled** Phone #: ###-####
FIR20-00209 INSP-Final Inspection4/2/20204/3/20204/3/2020 7:03:17 AMAPASS
Final fire alarm inspection for scope of work is complete.

As early as possible Phone #: 2086810381 >> Inspection requested via mobile web by Doug Lessa
FIR20-00144 INSP-Sprinkler Rough-in4/2/20204/3/20204/2/2020 2:53:10 PMPCANC
Contact Tanner Loomis ###-#### 30 min prior to RTC insp start please.

Thank YOU Phone #: ###-#### >> Inspection requested via web by Teri Cruickshank Inspection cancelled from web by: Teri Cruickshank
FIR20-00209 INSP-Final Inspection4/2/20204/3/20204/2/2020 9:42:55 AMPCANC
As early as possible Phone #: 2086810381 >> Inspection requested via mobile web by Doug Lessa Inspection cancelled via mobile web on Thursday, April 02, 2020.
FIR20-00209 INSP-Sprinkler Rough-in/Hydro4/2/20204/3/20204/2/2020 9:42:51 AMACANC
As early as possible Phone #: 2086810381 >> Inspection requested via mobile web by Doug Lessa Inspection cancelled via mobile web on Thursday, April 02, 2020.