Inspections for the day of: Wednesday, April 8, 2020.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD19-04869 FIRE-Final Inspection4/8/20204/8/20204/8/2020 1:13:40 PMPFAIL
Project is not ready for life fire safety inspection, fire sprinkler heads are covered with paint masking, exit light are masked for painting, test switch under masking, inspection request will need to be resheduled. Will need to verify mag-lock release on main entry doors during active fire alarm per 2015 IFC section 1010.1.9.8.



Phone #: ###-#### Inspection requested via web by Brad Zollinger
BLD19-03981 FIRE-Final Inspection4/7/20204/8/20204/8/2020 12:55:04 PMPPASS
Previously noted item has been corrected, no fire sprinklers, duct detection is complete (FIR20-00245) with no other fire alarm items, fire extinguishers are placed with current inspection tags. Final life fire safety inspection is complete, signature card not presented at time of inspection.

*screened* - Christian Phone #: ###-####
FIR19-00769 INSP-Sprinkler Rough-in/Hydro4/2/20204/8/20204/8/2020 12:53:27 PMAPART
Hydrostatic test has been witnessed, no pressure loss was observed. 24 hour air test started at 11AM @ 45PSI.

Please call Jim Lewis if any questions on this inspection he is on site Phone #: ###-#### Inspection requested via web by Joshua Hansen
FIR20-00245 INSP-Final Inspection4/7/20204/8/20204/8/2020 12:51:12 PMPPASS
Final inspection for scope of work is complete.

Please call Nate at ###-#### with inspection time. Phone #: ###-#### Inspection requested via web by Lori Brungardt
FIR20-00119 INSP-Sprinkler Rough-in4/6/20204/8/20204/8/2020 11:39:11 AMAPART
Rough in inspection for overhead fire sprinkler piping is complete, no tenting installed at time of inspection, cover is not approved.

Phone #: ###-#### Inspection requested via web by Jonathan Lee
FIR20-00120 INSP-Sprinkler Rough-in4/6/20204/8/20204/8/2020 11:38:32 AMAPART
Rough in inspection is complete, minor modifications/head additions was required to be compliant with NFPA13R, drawings to be submitted showing head additions/changes made. No tenting installed at time of inspection, cover is not approved.

Phone #: ###-#### Inspection requested via web by Jonathan Lee
FIR19-00769 INSP-Sprinkler Rough-in4/8/20204/8/20204/8/2020 10:36:41 AMAPART
Rough to cover inspection for overhead fire sprinkler piping in area of work is complete, approved for cover, except for data room. City approved drawings show a ceiling in the data room, as of this entry there is no ceiling and according to the point of contact a ceiling is not going to be installed. If no ceiling is installed then data room must comply with the 2016 NFPA13, section 8.15.23 or install ceiling as shown on city approved drawings with pendant protection.
FIR20-00228 INSP-Final Inspection4/7/20204/8/20204/8/2020 9:47:53 AMAPASS
Final fire sprinkler inspection for scope of work is complete.

Brad Zollinger will be there with the plans by 9:00am Phone #: ###-#### Inspection requested via web by Sam Ball
FIR20-00228 INSP-Sprinkler Rough-in4/7/20204/8/20204/8/2020 9:47:28 AMAPASS
Rough to cover inspection for scope of work is complete, approved for cover.

Brad Zollinger will be there with the plans by 9:00am Phone #: ###-#### Inspection requested via web by Sam Ball
BLD19-04498 FIRE-Final Inspection4/7/20204/8/20204/8/2020 9:31:32 AMAPASS
Fire sprinkler inspections (two different FIR permits for sprinkler modifications), no fire alarm modifications, fire extinguishers are placed with current inspection tags. Final life fire safety inspection is complete, signatures provided on permit sign off card.

Phone #: ###-#### Inspection requested via web by Todd Weltner
BLD19-01415 FIRE-Final Inspection4/7/20204/8/20204/8/2020 9:28:36 AMAPASS
Final life fire safety inspection for area of work complete.

screened // bruce Phone #: ###-####
FIR20-00190 INSP-Final Inspection4/7/20204/8/20204/8/2020 9:20:24 AMAPASS
Plans have been submitted, install matches city approved drawings, final inspection is complete.

Kenny Caldwell is the contact. Thanks for all your help! Phone #: ###-#### Inspection requested via web by Stan Beus
FIR19-00670 INSP-Final Inspection4/7/20204/8/20204/8/2020 8:03:04 AMAPASS
Final fire sprinkler inspection for scope of work is complete.

Troy Nelson Phone #: ###-#### Inspection requested via web by Brodie Stenquist