Inspections for the day of: Wednesday, June 24, 2020.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR19-00878 INSP-Final Inspection6/22/20206/24/20206/24/2020 4:07:53 PMPPASS
Final fire alarm inspection is complete.

Kc Strykowski, Tech Phone #: ###-#### Inspection requested via web by John Siewert
FIR19-00877 INSP-Final Inspection6/22/20206/24/20206/24/2020 4:07:21 PMPPASS
Final fire alarm inspection is complete.

Kc Strykowski, Tech Phone #: ###-#### Inspection requested via web by John Siewert
BLD19-02618 FIRE-Final Inspection6/23/20206/24/20206/24/2020 12:31:39 PMAFAIL
Correctly repair holes that were next to fire sprinkler heads in furnace closets. CPVC pipe is exposed in side entry closet under the stairs.

Phone #: ###-#### Inspection requested via web by bill gullickson
BLD19-02617 FIRE-Final Inspection6/23/20206/24/20206/24/2020 12:31:22 PMAFAIL
Correctly repair holes that were next to fire sprinkler heads in furnace closets. CPVC pipe is exposed in side entry closet under the stairs.

Phone #: ###-#### Inspection requested via web by bill gullickson
BLD19-02620 FIRE-Final Inspection6/23/20206/24/20206/24/2020 12:30:28 PMAPASS
Previously noted item has been corrected, final life fire safety inspection is complete.

Phone #: ###-#### Inspection requested via web by bill gullickson
FIR20-00061 INSP-Final Inspection6/23/20206/24/20206/24/2020 12:29:19 PMAPASS
Final fire sprinkler inspection is complete.

Call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
FIR20-00062 INSP-Final Inspection6/23/20206/24/20206/24/2020 12:28:58 PMAPASS
Final fire sprinkler inspection is complete.

James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
FIR19-00906 INSP-Supply line flush6/23/20206/24/20206/24/2020 10:55:26 AMANR
Flush was not performed due too the amount of wash-out that would happen from the jobsite to the public way, will area cleaned up for no wash out or provide means too flush without wash-out.

Coordinated with SUEZ and Jim for 10:30am, Gary or James will be on site ready to flush. Phone #: ###-#### Inspection requested via web by Anthony Minichiello
FIR19-00867 INSP-Final Inspection6/23/20206/24/20206/24/2020 9:15:37 AMAPASS
Final inspection complete.

Underground final. Phone #: ###-#### Inspection requested via web by Anthony Minichiello
FIR19-00864 INSP-Final Inspection6/23/20206/24/20206/24/2020 9:15:20 AMAPASS
Final inspection complete.

Underground Final Phone #: ###-#### Inspection requested via web by Anthony Minichiello
FIR20-00394 INSP-Sprinkler Rough-in6/23/20206/24/20206/24/2020 8:37:19 AMAPASS
Rough to cover inspection for area of work is complete, approved for cover.

Tony Cetani is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
FIR20-00414 INSP-Final Inspection6/23/20206/24/20206/24/2020 7:57:14 AMAFAIL
Small fryer on left side of hood does not fit under hood with compliant spacing, fryer will need to be removed or made compliant with the other appliances. Provide splash gaurd beteen large fryer and vertical broiler as discussed.

Screened- Nate Phone #: ###-####