FIR20-00148
| INSP-Final Inspection | 6/8/2020 | 6/9/2020 | 6/9/2020 3:40:28 PM | P | PASS |
|
|
Final fire sprinkler inspection is complete.
Contact: Jeremiah Robison Phone #: ###-#### Inspection requested via web by Hunter Fillmore
|
FIR20-00115
| INSP-Final Inspection | 6/8/2020 | 6/9/2020 | 6/9/2020 3:39:19 PM | P | PASS |
|
|
Final fire alarm inspection is complete.
Call prior to going Phone #: 2086810381 >> Inspection requested via mobile web by Doug Lessa
|
BLD20-00851
| FIRE-Final Inspection | 6/9/2020 | 6/9/2020 | 6/9/2020 1:05:53 PM | P | PASS |
|
|
No fire sprinklers, no fire alarms, fire extinguishers are placed with current inspection tags. Final life fire safety inspection for area of work is complete, signature provided on permit sign off card.
Call 20 minute before // Garrett Phone #: ###-####
|
FIR19-00836
| INSP-Sprinkler Rough-in/Hydro | 6/8/2020 | 6/9/2020 | 6/9/2020 11:08:38 AM | A | PART |
|
|
Areas inspected for rough in inspection are marked with green highlighter on city approved drawings. Cover inspection will be required after flex heads are installed in grid.
creened // John Phone #: ###-####
|
FIR19-00516
| INSP-Sprinkler Rough-in | 6/8/2020 | 6/9/2020 | 6/9/2020 10:11:06 AM | A | PART |
|
|
Rough to cover inspection for hardlids in rooms on level 7 compete, hardlids in rooms on level 7 approved for cover. Room drop down ceilings to be inspected after install.
Tony Cetani is the contact. This inspection is for the 7th floor Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR20-00120
| INSP-Final Inspection | 6/5/2020 | 6/9/2020 | 6/9/2020 9:37:31 AM | A | PASS |
|
|
Final fire sprinkler inspection is complete, irrigation shut-down on flow switch activation has been witnessed.
Phone #: ###-#### Inspection requested via web by Jonathan Lee
|
FIR20-00119
| INSP-Final Inspection | 6/5/2020 | 6/9/2020 | 6/9/2020 9:37:14 AM | A | PASS |
|
|
Final fire sprinkler inspection is complete, irrigation shut-down on flow switch activation has been witnessed.
Phone #: ###-#### Inspection requested via web by Jonathan Lee
|
FIR20-00132
| INSP-Final Inspection | 6/5/2020 | 6/9/2020 | 6/9/2020 9:36:21 AM | A | PASS |
|
|
Final fire sprinkler inspection is complete, irrigation shut-down on flow switch activation has been witnessed.
Phone #: ###-#### Inspection requested via web by Jonathan Lee
|
FIR20-00128
| INSP-Final Inspection | 6/5/2020 | 6/9/2020 | 6/9/2020 9:36:06 AM | A | PASS |
|
|
Final fire sprinkler inspection is complete, irrigation shut-down on flow switch activation has been witnessed.
Phone #: ###-#### Inspection requested via web by Jonathan Lee
|
FIR20-00125
| INSP-Final Inspection | 6/5/2020 | 6/9/2020 | 6/9/2020 9:35:18 AM | A | FAIL |
|
|
Hole was cut into ceiling in master bathroom, tenting has been removed from over top of pipe, area notated had no insulation on top of piping. Provide 175 degree head in master closet, head is within 24 inches of heat register.
Phone #: ###-#### Inspection requested via web by Jonathan Lee
|
FIR20-00120
| INSP-Sprinkler Rough-in/Hydro | 6/5/2020 | 6/9/2020 | 6/9/2020 9:33:47 AM | A | DONE |
|
|
Hydrostatic test for overhead fire srpinkler piping witnessed at city pressure, no pressure loss onserved at riser provided gauge.
Phone #: ###-#### Inspection requested via web by Jonathan Lee
|
FIR20-00119
| INSP-Sprinkler Rough-in/Hydro | 6/5/2020 | 6/9/2020 | 6/9/2020 9:33:30 AM | A | DONE |
|
|
Hydrostatic test for overhead fire srpinkler piping witnessed at city pressure, no pressure loss onserved at riser provided gauge.
Phone #: ###-#### Inspection requested via web by Jonathan Lee
|
FIR20-00132
| INSP-Sprinkler Rough-in/Hydro | 6/5/2020 | 6/9/2020 | 6/9/2020 9:33:10 AM | A | DONE |
|
|
Hydrostatic test for overhead fire srpinkler piping witnessed at city pressure, no pressure loss onserved at riser provided gauge.
Phone #: ###-#### Inspection requested via web by Jonathan Lee
|
FIR20-00128
| INSP-Sprinkler Rough-in/Hydro | 6/5/2020 | 6/9/2020 | 6/9/2020 9:32:53 AM | A | DONE |
|
|
Hydrostatic test for overhead fire srpinkler piping witnessed at city pressure, no pressure loss onserved at riser provided gauge.
Phone #: ###-#### Inspection requested via web by Jonathan Lee
|
FIR20-00125
| INSP-Sprinkler Rough-in/Hydro | 6/5/2020 | 6/9/2020 | 6/9/2020 9:32:24 AM | A | DONE |
|
|
Hydrostatic test for overhead fire srpinkler piping witnessed at city pressure, no pressure loss onserved at riser provided gauge.
Phone #: ###-#### Inspection requested via web by Jonathan Lee
|
FIR15-00804
| INSP-Final Inspection | 6/5/2020 | 6/9/2020 | 6/8/2020 2:38:34 PM | P | CANC |
|
|
Inspecting Technician: Ray McQueen Phone #: ###-#### >> Inspection requested via web by Rose Peterson Inspection cancelled from web by: Rose Peterson
|