FIR20-00232
| INSP-Final Inspection | 7/10/2020 | 7/14/2020 | 7/14/2020 3:07:25 PM | P | FAIL |
|
|
Provide weather proof enclosures for A/V devices in restrooms with showers (Boxes were being installed at time of inspection). Provide document cabinet as well as map showing initiating devices, map to be placed by fire alarm panel.
screened // Michael Phone #: ###-####
|
FIR19-00779
| INSP-Final Inspection | 7/14/2020 | 7/14/2020 | 7/14/2020 12:22:23 PM | A | CANC |
|
|
Cancelled per conversation with point of contact, could not final due too fire alarm inspection not being scheduled, inspection request will be rescheduled too conicide with fire alarm inspection.
Call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
FIR20-00375
| INSP-Sprinkler Rough-in/Hydro | 7/14/2020 | 7/14/2020 | 7/14/2020 11:06:27 AM | A | DONE |
|
|
Hydrostatic test witnessed, no pressure loss observed at riser provided gauge.
Call James before heading out, rough/hydro/tenting. Thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
FIR20-00375
| INSP-Sprinkler Rough-in | 7/14/2020 | 7/14/2020 | 7/14/2020 11:02:43 AM | A | PASS |
|
|
Previously noted items have been corrected, cover is approved. All tenting in place at time of inspection.
|
FIR20-00168
| INSP-Sprinkler Rough-in | 7/13/2020 | 7/14/2020 | 7/14/2020 10:30:09 AM | A | PART |
|
|
Rough to cover inspection from grid line 8 west is approved for cover, excluding main corridor located south side of building, grid is not installed.
Richard Clark is the contact. Phone #: ###-#### Inspection requested via web by Stan Beus
|