Inspections for the day of: Tuesday, August 11, 2020.
Number of inspections: 26
Percentage of inspections complete: 38 %
Percentage of inspections not complete: 62 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR12-00739 FIR-Aging Inspection8/5/20208/5/2020   
FIR12-00740 FIR-Aging Inspection8/5/20208/5/2020   
FIR13-00119 FIR-Aging Inspection8/5/20208/5/2020   
FIR14-00085 FIR-Aging Inspection8/5/20208/5/2020   
FIR14-00372 FIR-Aging Inspection8/5/20208/5/2020   
FIR15-00002 FIR-Aging Inspection8/6/20208/6/2020   
FIR15-00156 FIR-Aging Inspection8/6/20208/6/2020   
FIR13-00368 FIR-Aging Inspection8/7/20208/7/2020   
FIR14-00194 FIR-Aging Inspection8/7/20208/7/2020   
FIR14-00774 FIR-Aging Inspection8/7/20208/7/2020   
FIR08-00387 FIR-Aging Inspection8/10/20208/10/2020   
FIR13-00607 FIR-Aging Inspection8/10/20208/10/2020   
FIR14-00195 FIR-Aging Inspection8/10/20208/10/2020   
FIR14-00490 FIR-Aging Inspection8/10/20208/10/2020   
FIR20-00433 INSP-Sprinkler Rough-in8/11/20208/11/20208/11/2020 3:30:23 PMPPASS
Previously noted item has been repaired, rough to cover inspection is complete, approved for cover.

Coordinate Inspection with Rick Fry Thanks Phone #: ###-#### Inspection requested via web by Christophe Wilson
BLD20-02242 FIRE-Final Inspection8/11/20208/11/20208/11/2020 3:10:47 PMPPASS
Previously noted items have been corrected, slide bolt locks were removed from north door. Final life fire safety inspection is complete, signature provided on permit sign off card.

Ron *screened Phone #: ###-####
FIR19-00516 INSP-Sprinkler Rough-in/Hydro8/6/20208/11/20208/11/2020 1:35:44 PMPCANC
Tony Cetani is the contact. This hydro is for floors 2-5. Thank you for your hard work! Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
BLD19-04745 FIRE-Final Inspection8/11/20208/11/20208/11/2020 12:42:26 PMPCANC
Life safety complete on 04JUNE2020, this request is cancelled.

Phone #: ###-#### Inspection requested via web by rick pew Inspection cancelled from web by: rick pew
BLD20-01199 FIRE-Final Inspection8/7/20208/11/20208/11/2020 12:34:43 PMAPASS
No fire sprinkler modifications for area of work, no fire alarm modifications for area of work, fire extinguisher is placed with a current inspection tag. Final life fire safety inspection for area of work complete, signatures provided on permit sign off card.

Give Tom a call when in route. Phone #: ###-#### Inspection requested via web by tom mccalister
FIR19-00906 INSP-Sprinkler Rough-in8/11/20208/11/20208/11/2020 12:08:24 PMAFAIL
Provide auxiliary drain for head under rool up door. Add two uprights in discussed locations due top block head from duct work. Provide correct size fittings for exterior pipe per NFPA13 6.4.7. Add sway braing in areas marked on city approved drawings.

Call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
BLD20-02242 FIRE-Final Inspection8/10/20208/11/20208/11/2020 10:52:58 AMAFAIL
Provide annual inspection on fire extinguisher as discussed. Provide code compliant door hardware for north exit.

Ron *screened Phone #: ###-####
FIR20-00433 INSP-Sprinkler Rough-in8/10/20208/11/20208/11/2020 9:34:52 AMAFAIL
Low voltage wiring attached to fire sprinkler hangers in numerous areas.

Contact Mike Oswald to Coordinate inspection Phone #: ###-#### Inspection requested via web by Christophe Wilson
FIR20-00521 INSP-Sprinkler Rough-in/Hydro8/11/20208/11/20208/11/2020 9:33:43 AMAPART
Hydrostatic test for overhead fire sprinkler piping witnessed at city pressure, no pressure loss observed at riser provided gauge.

FIR20-00521 INSP-Sprinkler Rough-in8/10/20208/11/20208/11/2020 9:32:56 AMAPART
Rough in inspection is complete, tenting not installed at time of inspection.

Colton Cox is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
FIR15-00023 FIR-Aging Inspection8/11/20208/11/2020   
FIR15-00119 FIR-Aging Inspection8/11/20208/11/2020