Inspections for the day of: Tuesday, April 21, 2020.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTell Riley
TitleBLD-COM/RES INSPECTOR
Phone #830-2752
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD19-00534 BLD-Framing/Rough-in4/20/20204/21/20204/21/2020 3:55:19 PMPPART
Inspection on 3rd floor for approval to insulate and cover inspection on 4th floor Phone #: ###-#### Inspection requested via web by Travis Blackburn//4th floor ok to cover when fire collars are on drain pipe//3rd floor ok to insulate, fix sprinkler tenting, add fire collar to drain pipe, fix hole in joist in furnace room on two of the 4 units//
BLD20-01041 BLD-Foundation4/21/20204/21/20204/21/2020 3:40:19 PMPPART
Virtual Inspection Requested // Pat Phone #: ###-####//bar drilled to exisiting//wip//
BLD20-00670 BLD-Footing4/21/20204/21/20204/21/2020 2:14:51 PMPPART
picture of footing for point load was provided where it was needed, per the correction notice from wall inspection///appears to be rebar installed in the photo//
BLD19-03992 BLD-Framing/Rough-in4/21/20204/21/20204/21/2020 1:34:56 PMPPART
Willie - Soffit Inspection for Fire Protection Phone #: ###-####//ok to cover soffits//
BLD19-00532 BLD-Wall Bracing4/20/20204/21/20204/21/2020 12:38:44 PMAPART
Inspection for missed straps at south balconies for exterior cover. Phone #: ###-#### Inspection requested via web by Travis Blackburn//exterior straps nailed and exterior nailing ok//still need to check other hardware//
BLD19-00532 BLD-Framing/Rough-in4/20/20204/21/20204/21/2020 12:38:03 PMAPART
Partial framing inspection for 2hr lid in west corridor Phone #: ###-#### Inspection requested via web by Travis Blackburn//ok to install shaft liner//
BLD20-01184 BLD-Final4/17/20204/21/20204/21/2020 12:37:31 PMADONE
Inspection requested via web by Hans Weikl
BLD20-01184 DOC - Permit Finaled4/21/20204/21/20204/21/2020 12:37:21 PMPPASS
roof appears to be installed within code requirements//no access to back//
BLD19-04742 BLD-Footing4/15/20204/21/20204/21/2020 11:28:22 AMANR
Phone #: ###-#### Inspection requested via web by Ron Ramza//need approved plans and engineering onsite//
BLD20-00670 BLD-Wall Bracing4/20/20204/21/20204/21/2020 11:02:10 AMAFAIL
Need a shear wall inspection Phone #: ###-#### Inspection requested via web by David Thompson//CN posted, need to nails or staple with correct size staples front and rear shear walls//remove wrap in areas to verify staples//add hot dip galvanized nails at pt plate//add anchor bolts at plate ends//
BLD20-01163 BLD-Other4/20/20204/21/20204/21/2020 9:50:31 AMADONE
Inspection on a completed asphalt re-roof project. Phone #: ###-#### Inspection requested via web by Michael La Pointe
BLD20-01163 DOC - Permit Finaled4/21/20204/21/20204/21/2020 9:50:21 AMPPASS
Roof appears to be installed within code requirements//no access to back//
BLD19-04725 BLD-Wall Bracing4/20/20204/21/20204/21/2020 9:09:31 AMAPASS
Brian Phone #: ###-####//shear corrections made, engineers letter provided for corrections//
MIS20-00121 BLD-Conference4/20/20204/21/20204/21/2020 8:55:48 AMADONE
corrction notice posted to obtain permit for re-roof//