Name ST ALPHONSUS REG MED CEN INC
Site Address 6140 W CURTISIAN AVE Unit: 200
Project NameST AL'S-MOB #6
Customer Number 
ePlanReviewNo
Description
(ST ALPHONSUS MOB #6-IDAHO CARDIOLOGY ASSOCIATES)(2ND & 3RD FLOORS) New 31,172 sq. ft. tenant located on entire second and third floors of shell building done under BLD00-01744 for (B occupancy) medical office use and (I-1.2 occupancy) ambulatory/outpatient surgery center use per approved plans on file. Each floor is approximately 15,586 sq.ft. Work to include two-hour rated occupancy separation between B and I-1.2 occupancies, new two-hour rated stair shaft for new interior stairway between the 2nd and 3rd floors, spray-applied fire resistive materials on new steel structural members at new stair opening, new one-hour fire rated exit corridor, fire rated door installations where required, smoke/fire damper installations where required, structural support for medical equipment, one-hour rated medical gas room in basement of building, new accessible restrooms and shower rooms, new interior walls, new interior doors and windows, interior finish, access floor system in one room, new suspended ceiling installation, fire sprinkler work, fire alarm work, smoke detection work, new mechanical, new plumbing, and new electrical work. A CERTIFICATE OF OCCUPANCY IS TO BE ISSUED FOR THE TWO FLOOR TENANT WHEN WORK IS COMPLETED AND APPROVED. NOTE: This building is fully fire sprinklered. (P.C.#0379-01) JCB
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final2/20/20022/20/20022/20/2002PPASS
DetailsTom Arcoraci
###-#### doug ok for perm occ 2/20/2002 4:13:59 PM
Permanent Occupancy 2/20/20022/20/2002 DONE
Details
FIRE-Alarm Testing2/12/20022/12/20022/12/2002PPASS
DetailsTroy Cobbley
Fire alarm system finaled. 2/12/2002 4:57:44 PM
BLD-Final2/7/20022/8/20022/8/2002PPART
DetailsTom Arcoraci
###-#### doug ok for temp occ 2/8/2002 3:11:14 PM
FIRE-Final Inspection2/6/20022/8/20022/8/2002APART
DetailsTroy Cobbley
Fire life/safety and fire sprinkler finaled. Fire alarm given temp. occ. per Dave Miller. See FIR01-00551 for correction notice 2/8/2002 2:34:16 PM
FIRE-Final Inspection2/7/20022/7/20022/7/2002PFAIL
DetailsTroy Cobbley
Added by Inspector: 430 On 2/7/2002 12:26:28 PM Fire extinguishers need to be tagged. Door hardware, exit signs and emergency lights OK. Fire alarm to be tested later
BLD-Framing/Rough-in1/25/20021/25/20021/25/2002PPASS
DetailsTom Arcoraci
###-#### DOUG grid ok 2nd floor 1/25/2002 3:39:44 PM
BLD-Framing/Rough-in1/3/20021/3/20021/3/2002PPART
DetailsTom Arcoraci
###-#### 3RD FLOOR CEILING GRID grid ok check elec cond fire ck 1/3/2002 2:48:33 PM
BLD-Framing/Rough-in12/18/200112/19/200112/19/2001APART
DetailsTom Arcoraci
###-#### wip 12/19/2001 1:16:17 PM
BLD-Framing/Rough-in11/29/200111/30/200111/30/2001APART
DetailsTom Arcoraci
DOUG ###-#### fire chalk ok at vert beams ok to cover them 11/30/2001 11:26:04 AM
BLD-Conference11/15/200111/16/200111/16/2001PPASS
DetailsTom Arcoraci
Scheduled by Inspector: 408 On 11/15/2001 12:04:00 PM 1 pm meeting
BLD-Conference11/7/200111/7/200111/7/2001AFAIL
DetailsTom Arcoraci
Scheduled by Inspector: 408 On 11/7/2001 11:03:41 AM stop work issued for 3rd floor at 1 and 2 hr walls where they contact fire proof struc members 11/7/2001 11:51:25 AM 11/7/2001 11:51:43 AM
BLD-Concrete10/29/200110/30/200110/30/2001AFAIL
DetailsTom Arcoraci
###-#### DOUG 2ND FLOOR need ok from supervisor for eng judgement on two hr fire stop 10/30/2001 10:23:14 AM
BLD-Framing/Rough-in10/16/200110/17/200110/17/2001PFAIL
DetailsTom Arcoraci
3rd floor Partial\\###-#### need new assm for 2 hr occ wall, need to frame around struc beams at 2 hr occ wall and 1 hr corr walls 10/17/2001 5:16:29 PM
BLD-Conference10/2/200110/9/200110/9/2001APASS
DetailsTom Arcoraci
Scheduled by Inspector: 408
10/9/2001 3:15:56 PM smk/fire to be installed in 2-hr occ wall south side 10/9/2001 3:16:39 PM
BLD-Framing/Rough-in10/1/200110/2/200110/2/2001APART
DetailsTom Arcoraci
###-#### 3rd floor 2- hr occ needs smoke fire damper 10/2/2001 10:37:33 AM
BLD-Framing/Rough-in9/28/20019/28/20019/28/2001PCANC
DetailsRuss Owen
partial on 3rd flr ###-####