BLD-Final | 2/20/2002 | 2/20/2002 | 2/20/2002 | P | PASS |
Tom Arcoraci
|
|
|
###-#### doug ok for perm occ 2/20/2002 4:13:59 PM
|
Permanent Occupancy | | 2/20/2002 | 2/20/2002 | | DONE |
|
|
|
|
FIRE-Alarm Testing | 2/12/2002 | 2/12/2002 | 2/12/2002 | P | PASS |
Troy Cobbley
|
|
|
Fire alarm system finaled. 2/12/2002 4:57:44 PM
|
BLD-Final | 2/7/2002 | 2/8/2002 | 2/8/2002 | P | PART |
Tom Arcoraci
|
|
|
###-#### doug ok for temp occ 2/8/2002 3:11:14 PM
|
FIRE-Final Inspection | 2/6/2002 | 2/8/2002 | 2/8/2002 | A | PART |
Troy Cobbley
|
|
|
Fire life/safety and fire sprinkler finaled. Fire alarm given temp. occ. per Dave Miller. See FIR01-00551 for correction notice 2/8/2002 2:34:16 PM
|
FIRE-Final Inspection | 2/7/2002 | 2/7/2002 | 2/7/2002 | P | FAIL |
Troy Cobbley
|
|
|
Added by Inspector: 430 On 2/7/2002 12:26:28 PM Fire extinguishers need to be tagged. Door hardware, exit signs and emergency lights OK. Fire alarm to be tested later
|
BLD-Framing/Rough-in | 1/25/2002 | 1/25/2002 | 1/25/2002 | P | PASS |
Tom Arcoraci
|
|
|
###-#### DOUG grid ok 2nd floor 1/25/2002 3:39:44 PM
|
BLD-Framing/Rough-in | 1/3/2002 | 1/3/2002 | 1/3/2002 | P | PART |
Tom Arcoraci
|
|
|
###-#### 3RD FLOOR CEILING GRID grid ok check elec cond fire ck 1/3/2002 2:48:33 PM
|
BLD-Framing/Rough-in | 12/18/2001 | 12/19/2001 | 12/19/2001 | A | PART |
Tom Arcoraci
|
|
|
###-#### wip 12/19/2001 1:16:17 PM
|
BLD-Framing/Rough-in | 11/29/2001 | 11/30/2001 | 11/30/2001 | A | PART |
Tom Arcoraci
|
|
|
DOUG ###-#### fire chalk ok at vert beams ok to cover them 11/30/2001 11:26:04 AM
|
BLD-Conference | 11/15/2001 | 11/16/2001 | 11/16/2001 | P | PASS |
Tom Arcoraci
|
|
|
Scheduled by Inspector: 408 On 11/15/2001 12:04:00 PM 1 pm meeting
|
BLD-Conference | 11/7/2001 | 11/7/2001 | 11/7/2001 | A | FAIL |
Tom Arcoraci
|
|
|
Scheduled by Inspector: 408 On 11/7/2001 11:03:41 AM stop work issued for 3rd floor at 1 and 2 hr walls where they contact fire proof struc members 11/7/2001 11:51:25 AM 11/7/2001 11:51:43 AM
|
BLD-Concrete | 10/29/2001 | 10/30/2001 | 10/30/2001 | A | FAIL |
Tom Arcoraci
|
|
|
###-#### DOUG 2ND FLOOR need ok from supervisor for eng judgement on two hr fire stop 10/30/2001 10:23:14 AM
|
BLD-Framing/Rough-in | 10/16/2001 | 10/17/2001 | 10/17/2001 | P | FAIL |
Tom Arcoraci
|
|
|
3rd floor Partial\\###-#### need new assm for 2 hr occ wall, need to frame around struc beams at 2 hr occ wall and 1 hr corr walls 10/17/2001 5:16:29 PM
|
BLD-Conference | 10/2/2001 | 10/9/2001 | 10/9/2001 | A | PASS |
Tom Arcoraci
|
|
|
Scheduled by Inspector: 408
10/9/2001 3:15:56 PM smk/fire to be installed in 2-hr occ wall south side 10/9/2001 3:16:39 PM
|
BLD-Framing/Rough-in | 10/1/2001 | 10/2/2001 | 10/2/2001 | A | PART |
Tom Arcoraci
|
|
|
###-#### 3rd floor 2- hr occ needs smoke fire damper 10/2/2001 10:37:33 AM
|
BLD-Framing/Rough-in | 9/28/2001 | 9/28/2001 | 9/28/2001 | P | CANC |
Russ Owen
|
|
|
partial on 3rd flr ###-####
|