BLD-Final | 10/2/2001 | 10/3/2001 | 10/3/2001 | A | PASS |
Jim Storey
|
|
|
greg ###-#### final ok per approved plan. 10/3/2001 9:28:51 AM
|
FIRE-Final Inspection | 8/28/2001 | 8/28/2001 | 8/28/2001 | A | PASS |
Rick Jackson
|
|
|
Added by Inspector: 409 On 8/28/2001 7:11:06 AM
|
BLD-Final | 8/27/2001 | 8/27/2001 | 8/27/2001 | P | PART |
Jim Storey
|
|
|
Added by Inspector: 301 On 8/27/2001 4:29:57 PM ok for use/ corner berriors req./ s.e gaurd railling up 1 inch to 42 min.
|
BLD-Conference | 8/17/2001 | 8/17/2001 | 8/17/2001 | A | FAIL |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 08/17/2001 at 06:34:31. Contact: ###-####. notes to 8/15 responce blong on this action. 8/17/2001 10:06:59 AM
|
FIRE-Conference | 8/16/2001 | 8/17/2001 | 8/17/2001 | A | PART |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 08/16/2001 at 20:21:52. Contact: ###-####. requirements for obtaining occupancy with Jim Storey 8/17/2001 12:24:48 PM
|
BLD-Conference | 8/15/2001 | 8/15/2001 | 8/15/2001 | P | FAIL |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 08/15/2001 at 11:05:54. Contact: ###-####. fire dept. mandated that draft curtins be removed. approved plan are specific to location of draft curtins architect to resolve isue with plan reviewers no occupance until resolved/ no storage on racking allowed until approval from bld. dept. 8/17/2001 9:58:21 AM
|
FIRE-Conference | 8/15/2001 | 8/15/2001 | 8/15/2001 | P | PART |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 08/15/2001 at 11:05:04. Contact: ###-####. ddiscuseed moving requirements with Pat; told him to talk to Jim Storey about his requirements 8/15/2001 2:28:37 PM
|