BLD-Final | 3/11/2002 | 3/12/2002 | 3/12/2002 | A | PASS |
Jim Storey
|
|
|
###-#### TIM final ok 3/12/2002 9:35:11 AM
|
Permanent Occupancy | | 3/12/2002 | 3/12/2002 | | DONE |
|
|
|
|
BLD-Final | 3/7/2002 | 3/8/2002 | 3/8/2002 | P | PART |
Jim Storey
|
|
|
fn occ- tim ###-#### temp ok pending plm and health dept. perm sign off. 3/8/2002 4:54:24 PM
|
FIRE-Final Inspection | 3/7/2002 | 3/7/2002 | 3/7/2002 | P | PASS |
Rick Jackson
|
|
|
fire fn ###-#### cell
|
FIRE-Final Inspection | 3/4/2002 | 3/6/2002 | 3/6/2002 | P | FAIL |
Rick Jackson
|
|
|
fire fn- john ###-#### kitchen extinguishing systems tested okay; air balance okay; exit signs didn't have battery back up - only issue left for fire final 3/6/2002 3:00:26 PM
|
Code Occupancy Approval | 3/5/2002 | 3/5/2002 | 3/5/2002 | A | PASS |
Wm. Michael Meloy
|
|
|
Scheduled by Inspector: WMM On 3/5/2002 11:58:37 AM
|
BLD-Framing/Rough-in | 2/28/2002 | 3/1/2002 | 3/1/2002 | A | PASS |
Russ Owen
|
|
|
Scheduled by Inspector: 408 On 2/28/2002 4:47:58 PM tim 2490837 grid
|
BLD-Framing/Rough-in | 2/27/2002 | 2/28/2002 | 2/28/2002 | P | CANC |
Tom Arcoraci
|
|
|
TIM ###-#### CELING GRID
|
FIRE-Alarm Testing | 2/25/2002 | 2/27/2002 | 2/27/2002 | P | PART |
Troy Cobbley
|
|
|
Hood in the A&W section operated correctly but is missing the hood balance report. The KFC hood was not entirely piped but did shut down power and gas. It is missing the air balance reports as well. No alarms were tested. There are live exposed wiring in the valve box of the KFC hood. Contractor to install signs to designate manual pull stations 2/27/2002 2:29:56 PM
|
BLD-Framing/Rough-in | 2/19/2002 | 2/19/2002 | 2/19/2002 | P | PASS |
Jim Storey
|
|
|
###-#### roof equment screening ok for cover/ shaft wrap ok. 2/19/2002 4:24:54 PM
|
BLD-Framing/Rough-in | 2/4/2002 | 2/5/2002 | 2/5/2002 | A | FAIL |
Jim Storey
|
|
|
for fire master on grease duct--robin ###-#### fast wrap product not approved for ubc es report listing, only southern . 2/5/2002 2:29:12 PM
|
BLD-Framing/Rough-in | 1/25/2002 | 1/25/2002 | 1/25/2002 | P | PART |
Jim Storey
|
|
|
###-#### interior walls ok for cover. 1/25/2002 4:54:28 PM
|
BLD-Framing/Rough-in | 1/23/2002 | 1/23/2002 | 1/23/2002 | P | PART |
Jim Storey
|
|
|
###-#### ok to cover interior upon approval in dinning area/ exterior ok for cover on brick and ifis. 1/23/2002 3:19:17 PM
|
BLD-Framing/Rough-in | 1/16/2002 | 1/17/2002 | 1/17/2002 | A | PART |
Jim Storey
|
|
|
###-#### ok to cover exterior and start massonary. 1/17/2002 9:34:52 AM
|
BLD-Foundation | 12/20/2001 | 12/24/2001 | 12/24/2001 | A | PASS |
Russ Owen
|
|
|
###-####
|
BLD-Footing | 12/20/2001 | 12/21/2001 | 12/21/2001 | A | PASS |
Steven Webb
|
|
|
###-####
|