Permit Information
Permit NumberBLD01-02690
StatusFinaled
Name YEN CHING
Site Address 305 N 9TH ST
Project NameYEN CHING
Customer Number 
ePlanReviewNo
Description
(YEN CHING) New additional Type I hood installation and cooking equipment in the bar area of existing 5,873 sq. ft. assembly restaurant per approved plans on file. Work to include new Type I hood with one-hour rated duct enclosure, mechanical work including rooftop equipment, and electrical work. This is a Scope of Work Permit. LETTER OF COMPLETION TO BE ISSUED WHEN DONE. NOTE: This building is NOT fire sprinklered. (PC#0791-01) JCB
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
FIRE-Final Inspection1/10/20021/10/20021/10/2002PPASS
DetailsRick Jackson
###-#### air balance report on site and meets design specs. 1/10/2002 2:11:15 PM
BLD-Final1/8/20021/8/20021/8/2002PPART
DetailsCarl Dependahl
###-####, struct ok , has firemaster wrap at duct; need air balance 1/8/2002 4:05:45 PM
BLD-Final1/3/20021/3/20021/3/2002PNR
DetailsCarl Dependahl
###-#### OR ###-####
FIRE-Final Inspection12/27/200112/31/200112/31/2001AFAIL
DetailsTroy Cobbley
need air balance reports, knox box 12/31/2001 10:13:21 AM
BLD-Conference12/28/200112/28/200112/28/2001PPART
DetailsCarl Dependahl
Added by Inspector: 340 On 12/28/2001 12:12:04 PM w/ bldr, need extiguisher tests